Daily inspection is the first line of defence, yet many checklists decay into ritual. This page provides a checklist organised by the five senses — look, listen, touch, smell, measure — each item with a criterion and an action when exceeded.
Three tiers: pre-shift (two minutes — displays, sounds, smells), daily rounds (10-15 minutes on the checklist), and professional inspection (monthly or quarterly with instruments). The five senses do the daily work: look at indicators, displays, dust, water traces and burn marks; listen for fan noise, contactor hum, transformer tone changes and discharge hissing; touch housings with the back of the hand (comfortable for 3 seconds means below about 60 C); smell for scorched varnish and ozone; measure with spot pyrometers and clamp meters on key points. Any sensory finding gets instrument confirmation — never conclude from feel alone. Records are written on the spot, anomalies photographed and turned into work orders; that is what separates inspection from a walk.
The checklist by object. Cabinets: surface temperature and smell, fan and filter state, indicator lamps (a lit fault LED gets logged), door seals and locks, condensation signs. Motors: housing temperature (back-of-hand or pyrometer, under 80 C for class B), bearing grit or rubbing noises, vibration (often the earliest bearing warning), terminal box seals, earth strap condition. Drives and VFDs: fan sound, display codes, heatsink temperature (track anything over 70 C), output cable condition. Terminals and busbars: infrared spot checks on visible joints (over 20 K rise gets a tag). Cables and trays: sheath damage, heat discolouration, standing water. Safety devices: e-stop buttons and curtain indicators intact (function tests belong to专项 rounds). Budget about 30 seconds per item and 15 minutes per cabinet; longer means the list is too heavy.
Value lives in the trend: pool temperature, current and noise weekly and plot curves; three consecutive one-way deteriorations schedule maintenance before the alarm does. Close every anomaly: find, open a numbered work order immediately, repair and feed back, recheck and close. Revise the list continuously — items clean for three months drop in frequency, repeat offenders gain checks. Calibrate the inspectors: align feel against the pyrometer in quarterly joint rounds. Three anti-ritual measures: handwritten on-site sheets only, photos mandatory for anomalies, and a foreman re-inspecting two machines weekly.
| Object | Check | Criterion | Action if exceeded |
|---|---|---|---|
| Control cabinet | Temp, smell, fans | No burning smell, fans normal | Open work order |
| Motor housing temp | Hand or pyrometer | ≤80 C (class B) | Check load and cooling |
| Motor noise and vibration | Senses plus vibration pen | No grit or rubbing | Schedule bearing check |
| Drive heatsink | Temp and codes | ≤70 C, no fault codes | Clean filter, check airflow |
| Terminals and busbars | Infrared spot check | Rise ≤20 K | Tag, track and re-torque |
| Cables and trays | Sheath and water | No damage, no staining | Open work order |
| Safety devices | E-stop and curtain LEDs | Intact, indicators normal | Call专项 inspection |
| Earthing bonds | Visual for rust and looseness | Sound and tight | Fix immediately |
For building a daily electrical inspection system. Three principles: record on the spot, quantify every anomaly and open a work order, and feed the data into trend analysis. Design the list to fit 15 minutes, senses first with instrument confirmation, and keep fidelity with foreman sampling.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance context per GB/T 5226.1 (IEC 60204-1) and electrical safety per GB/T 13869; condition monitoring per the relevant vibration and infrared diagnostic industry standards. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.