The datasheet says 1200 metres, the bus drops frames after three hundred. Cable, baud rate, termination and topology hold the answer - and five fixes ordered by cost.
The loss of range usually traces to one of six things: wrong cable - the bus needs 120-ohm characteristic impedance shielded twisted pair, not odd lengths of trailing shield; baud rate against distance - 115200bps is reliable only for tens to a couple of hundred metres; a star topology whose branches reflect; missing or duplicated termination - exactly 120 ohms at each end, nowhere else; more than 32 nodes without a repeater; and interference from parallel power runs with poor shield earthing.
Widen the reach in cost order: drop the baud rate first - 9600 or even 4800 doubles or quadruples the distance, and most metering traffic never notices; re-cable in proper 120-ohm screened twisted pair; fit 120-ohm terminators at the two bus ends (measuring about 60 ohms across A-B proves both are present); add repeaters, each extending 1200 metres and another 32 nodes; go optical for kilometres or brutal interference, with converters isolating ground potential completely. Accept with numbers: differential swing above 1.5V on a scope, error frames under one in ten thousand over an hour, and a retest with every machine running - the worst-case electromagnetic environment is the only one that counts.
| Symptom | Points to | Verification | Action |
|---|---|---|---|
| Drops past half the distance | Baud too high for the run | Test at lower baud | Slow down or repeat |
| Reflected edges, odd errors | Termination wrong | A-B impedance about 60 ohms | 120 ohms at both ends |
| Errors cluster on branches | Star topology reflections | Review the topology | Rebuild as a daisy chain |
| Errors when big motors start | Power cable interference | Scope the glitch timing | Screened cable, separation |
| Unstable with many nodes | Beyond 32 nodes | Count online nodes | Add a repeater segment |
Slow down, re-cable, terminate, repeat, then optical - cheapest first, retest each step. Eight of ten RS485 troubles live in the cable and the terminators, not in the devices.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Balanced multipoint signalling per TIA/EIA-485, industrial network practice per GB/T 19582 (Modbus) series, machinery communication per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.