Two devices answering one address can stall a whole network. The typical signatures, four ways to pin the culprit, and the address plan that stops the next clash before it happens.
Clashes show three ways: two slaves sharing an address produce mixed replies - checksum errors, timeouts, data right one moment and wrong the next; a master overlapping a slave address gets its own frames answered, wedging the bus; a new device joining with a taken address drops the whole network that was fine before. And there is the false clash: correct addresses but the master reading the wrong register area, which behaves identically. The quickest test is physical - unplug the suspect and watch the fault vanish.
Find it with four tools: the master configuration table against each device dial or parameter - the overlap stands out; a bus sniffer on a USB converter showing alternating replies from one address; power-cycling from the far end until the bus recovers, bracketing the pair; and the dial check - instruments often ship with address 1 set, straight out of the box onto a live bus. Then write it down: every device with address, baud and parity on a sheet inside the cabinet. House rules keep it fixed: planned address blocks per bus, new devices drawn from the plan and answered before joining, master configuration updated in step, and a quarterly reconciliation of sheet versus dials.
| Symptom | Cause | How to pin | Action |
|---|---|---|---|
| Data right then wrong, CRC errors | Two slaves, one address | Sniff the replies | Change a slave address |
| Bus wedged, fake online | Master address overlaps | Check master setting | Separate the ranges |
| Network dies as new device joins | Address already taken | Unplug and verify | Redraw from the plan |
| Wrong register data | Register area misconfigured | Compare the device map | Fix master configuration |
| One instrument drops in and out | Dirty or loose DIP switch | Reseat and clean | Replace or secure |
Plan first, number from the plan, verify before joining, reconcile quarterly. Address clashes are the cheapest faults to prevent and the most expensive to chase on a dead network.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Industrial networks per GB/T 19582 (Modbus) series and the IEC 61158 fieldbus series, machinery communication per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.