What does 380V△/660VY on a nameplate actually mean? This page decodes every field, ties the dual voltage to the winding connection, and gives quick estimation rules for rated current.
A dual marking of 380V delta and 660 V star means the same phase winding sees 380 V across it in either case; the line voltage differs. On a 380 V grid the motor must be delta-connected; star-connecting it puts 1/√3 of rated voltage per phase, torque collapses to a third and the stalled winding burns within minutes. Reverse the mistake on a 660 V grid and the insulation suffers overvoltage. In the terminal box, three links in a vertical bar make star, two links per column make delta, and the nameplate always beats the shape of the old links.
Rated current is the line current at rated voltage, power, efficiency and power factor, from I = P/(√3·U·η·cosφ). A practical rule of thumb on 380 V is about 2 A per kW, 15 A for 7.5 kW, near 105 A for 55 kW. Where a single current is given it belongs to the delta connection at the corresponding voltage; dual figures such as 15.4/8.9 A correspond to delta and star respectively, a factor of √3 apart. On a VFD, judge loading from the actual output current, not the line-frequency nameplate.
Other fields earn their place: 1440 r/min indicates four poles with 4 percent slip and provides the baseline for fault checks; insulation class F caps the winding at 155 C; IP55 resists dust and spray while IP23 does not, so outdoor machines below IP54 die early. Duty type S1 is continuous while S3-40% allows only 40 percent cycling, and running an S2 machine continuously is a classic burnout. Efficiency class IE3 saves about 3000 kWh a year on a 30 kW motor running 6000 hours.
| Field | Example | Meaning | Field use |
|---|---|---|---|
| Rated power | 7.5 kW | Shaft output | Load matching |
| Rated voltage | 380V△/660VY | Line voltage per connection | Wiring basis |
| Rated current | 15.4 A | Line current at rating | Protection setting |
| Rated speed | 1440 r/min | 4 poles, 4% slip | Fault baseline |
| Insulation class | F | 155 C ultimate | Rise judgement |
| Protection grade | IP55 | Dust and spray tight | Environment fit |
| Duty type | S1 | Continuous | Load pattern match |
Photograph and archive every nameplate. Set thermal protection at 1.05 to 1.1 times rated current, and recheck grid voltage and protection settings whenever the connection is changed, followed by an unloaded run to confirm balanced currents.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 755 for nameplate ratings and IEC 60204-1 for wiring safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.