An earth-fault trip on the drive could be the motor, the cable or the drive itself. The detection logic, the three-way split, and the safety rules that keep the housing from biting someone.
Drives detect earth faults from the instantaneous sum of output currents - zero in healthy three-phase operation - or from bus midpoint shift; above a threshold of a few amps to tens of amps the output blocks and the motor coasts, which matters for hoisting loads with brakes. Distinguish it from overcurrent: overcurrent is phase-to-phase or load trouble, earth fault is to-frame trouble. Low-power drives with midpoint sensing are less sensitive, and a light fault may show only as unbalance - so an unbalance alarm deserves a moment of suspicion too.
Split three ways. First the drive itself: disconnect the motor cable and start unloaded - the alarm gone means cable or motor, still present means internal detection or module, send it for service. Then the cable: with both ends open, megger the cores to earth at 500V - below 0.5 megohm, find the damaged run, usually abrasion in conduit, water or rodents. Then the motor: per-phase to earth at the terminal box, and treat damp or punctured windings as in the earth-fault chapter. The one absolute: never megger onto the drive terminals - 500V kills the IGBTs. After clearing, run unloaded, then jog coupled at low speed, confirm rotation, then load stepwise, keeping everyone clear and the lockout in place until proven.
| Object | Method | Pass criterion | If failed |
|---|---|---|---|
| Drive itself | Start unloaded, motor cable off | Alarm gone | Still alarming: service or swap |
| Output cable | 500V megger to earth | Above 0.5 megohm | Locate damage, remake run |
| Motor winding | Phase to earth at terminal box | Above 0.5 megohm | Dry out, or rewind |
| Terminals and wiring | Visual plus insulation check | No damage, no frame contact | Re-route and protect |
| Earthing system | PE continuity measured | Below 0.1 ohm | Retighten or remake bond |
Disconnect first, split second, cable before motor. The megger never touches the drive. No re-energising until the fault is cleared - a live frame risk makes lockout and a watcher non-negotiable.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Safety of adjustable speed drives per GB/T 12668.501 (IEC 61800-5-1) and GB/T 5226.1 (IEC 60204-1), motor insulation per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.