Knowledge Base › Electrical Knowledge Base › Setting drive overload protection properly: reference current, thermal curve and low-speed derating
HomeModels
Table of contents

On this page

Fault Diagnosis & Standards (100 articles)

Quick Reference

  • PLC & Programming
  • Electrical & Electronic Basics (monthly)(每月更新中)
  • Electrical Control & Drawings (monthly)(每月更新中)
  • Drives & Actuators (monthly)(每月更新中)
  • Sensors & Detection (monthly)(每月更新中)
  • Industrial Communication & Networks (monthly)(每月更新中)
  • HMI & Host Systems (monthly)(每月更新中)
  • Industrial Robots & Motion Control (monthly)(每月更新中)
  • Mechatronic System Integration (monthly)(每月更新中)
  • Fault Diagnosis & Standards (monthly)(每月更新中)

Setting drive overload protection properly: reference current, thermal curve and low-speed derating

Overload protection set wrong either nags all day or sleeps through a burned motor. The parameter trio, the nameplate rule, low-frequency derating math and the verification that proves it works.

1. How it works

Three parameters define the protection: the current reference (Pr.9 on Mitsubishi, P0640-class on Siemens, brand equivalents elsewhere), the thermal characteristic, and the action - trip or current limit. The iron rule: reference from the motor nameplate, never the drive rating. Drives are usually sized a frame above the motor, so the factory value overshoots by 20~50 percent - left alone, the motor runs unprotected. One drive feeding several motors cannot watch each one: every motor gets its own thermal relay, and the drive overload is set to the total current with the cable ampacity checked.

2. Practice and pitfalls

Thermal characteristics split by cooling: self-cooled motors lose cooling at low speed, so either select the self-cooled curve, or derate the reference 10~20 percent for long operation below 20Hz (cooling at 20Hz is roughly 60~70 percent of rated, about 80 percent at 30Hz), or fit an independent fan; inverter-duty motors with forced cooling take the constant-torque curve. Then verify: run to thermal equilibrium at full load with frame and winding within the insulation class, prove that 120 percent for five minutes alarms or trips, and keep the chain sane - electronic thermal as primary, a thermal relay on the output as backup, cable ampacity for the wiring, upstream breaker for shorts. Record every value with author and date, and re-verify whenever the motor is exchanged.

3. Overload setting quick table

ItemCorrect practiceCommon errorVerification
Current referenceMotor nameplate currentFactory drive value keptCheck against nameplate
Thermal curveSelf-cooled or forced, chosenDefault curve for everythingLow-speed heat run
Low-speed deratingMinus 10~20 percent below 20HzFull current at low speedThermal equilibrium test
Multi-motor drivesIndividual relays per motorElectronic thermal onlyTrip test on each
Backup protectionOutput thermal relay as backupBackup removed as redundantPeriodic relay check

4. Notes

Reference to the nameplate, curve by cooling, discount at low speed, backup in place, verify after every change. The overload chain is the last gate before a cooked winding - values with authors and dates make it trustworthy.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive protection per GB/T 12668.2 (IEC 61800-2), motor ratings and temperature limits per GB/T 755, thermal overload coordination per GB/T 14048.4. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Keeping the factory current reference: 20~50 percent too high and the motor burns silently - set from the nameplate
② Running low-speed duty at full reference: self-cooled motors lose a third of their cooling below 20Hz - derate or add a fan
③ Relying on the electronic thermal for multi-motor drives: a small overloaded motor goes unnoticed - individual relays mandatory

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.