Visual inspection items for electrical rounds

Visual checks are the cheapest part of inspection and the easiest to fake: what to look at, and what counts as abnormal, needs explicit criteria. This page splits visual inspection into ten signal types, each with abnormal features and handling.

1. How it works

Ten signal types. Discolouration: yellowed or blackened insulation, heat-stained terminals, blistered cable sheaths — all overheating marks. Burning: pitted contacts, arc traces on busbars, carbonised tracking on insulators. Dust: filters too caked to see light through, surface film inside cabinets, conductive dust bridging terminals in dusty shops. Water and rust: wet cabinet floors, rust weeps, seeping glands. Deformation: buckled enclosures, sagging trays, cracked insulators. Looseness: conductors backing out, crimps sliding free, broken ties dropping harnesses. Leakage: oil film near hydraulics, bulging electrolytic capacitors weeping electrolyte. Indicator faults: lit fault LEDs, phase lamps wrong, level gauges low. Missing parts: absent covers, screws, labels and plugs. Environment: storage against cabinets, blocked aisles, obstructed vents.

2. Numbers and practice

Quantifying the judgement: slight yellowing of insulation allows continued running with a tracking note, blackening or blistering means act now; filters washed when light no longer passes, dust between terminals cleaned with power off; a damp floor with no standing water gets ventilation the same day, standing water or drips mean de-energise first; surface rust gets wire-brushed and painted, structural perforation or a rusted-through door strap means replacement; insulator cracks or tracking marks mean immediate removal; bulging DC-link capacitors have lost 20 percent or more of capacity and get replaced. Photograph every finding. The same signal recurring at the same spot is a system problem — insufficient cooling, overload or wrong environmental rating.

3. Pitfalls and fixes

Organisation and tools: a torch for cabinet corners, a mirror for busbar backs, a magnifier for cracks and tracking, a camera with numbered photos, a spot pyrometer for instant confirmation. Fix the route per machine (surface, interior, base, wiring zone, surroundings) so nothing is skipped. Frequency by environment: weekly in normal shops, daily in dusty or wet areas, monthly outdoors plus after every rain. Design the record sheet around the ten signals with tick boxes and anomaly numbers. Train newcomers on ten joint rounds with a photo library of typical discolouration, dust and cracks. Visual screening and instrument confirmation are a pair — each is worthless without the other.

4. Visual inspection signals quick reference

SignalAbnormal featureSeverityAction
DiscolourationBlackened insulation, stained terminalsYellow tracks, black acts nowConfirm with pyrometer
BurningPitted contacts, tracking marksRemove from serviceReplace contacts and insulators
DustOpaque filters, dusty terminalsWash when cooling suffersClean with power off
Water and rustWet floor, rust weepsDe-energise on standing waterSeal and dry
CracksInsulator cracks, trackingImmediate replacementSwap the part
Bulging capacitorsDomed tops, leaked electrolyteOver 20 percent lossSchedule replacement
Missing partsCovers, screws, plugs goneRestore IP integrityRefit and log
EnvironmentStorage and blocked ventsClear immediatelyOn-site rectification

5. Notes

For the visual component of any inspection system. The ten signals are the shared language: train against a photo library, record by signal type, photograph with numbers. Visual findings screen, never conclude — confirm with the pyrometer or instruments before acting.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance per GB/T 5226.1 (IEC 60204-1); enclosure integrity per GB/T 4208; electrical safety per GB/T 13869. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Logging discolouration without measuring the temperature: yellowed and blackened are different worlds; confirm with the pyrometer first
② Ignoring water marks under the cabinet: they are the early sign of seepage, and standing water plus live busbars ends badly; seal the day you see it
③ Leaving missing covers and plugs unfixed for months: an open invitation for dust and water that erases the IP rating; refit from a spares list

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.