Whether to earth the shield at one end or both has been argued on site for decades. The answer depends on frequency: single-ended stops ground loops at low frequency, double-ended is the only thing that works at high frequency. This page explains both mechanisms, their frequency ranges, and what happens when they are mixed up.
Double-ended earthing bonds the shield at both ends, which is what makes it effective above roughly 1 MHz: radiated coupling dominates there, and a shield grounded at both ends forms a low-impedance loop whose induced current creates an opposing field that cancels the interference. The catch is the ground loop itself: plant earths routinely differ by 1 to 10 V, and with shield resistance of tens of milliohms per metre even a few volts drives ampere-level circulating current that wrecks low-frequency signals. Single-ended earthing cuts that loop and works well against low-frequency electric-field coupling (50 Hz and harmonics, static induction), but loses most of its magnetic shielding at high frequency.
Rules of thumb by bandwidth: below 100 kHz — 4-20 mA analog, thermocouples, RTDs, load cells — earth single-ended at the receiving cabinet, leaving the source end floating. Above 100 kHz — encoder pulses, communication buses, fast digital signals — earth both ends with a 360-degree gland bond, never a pigtail. Communication cables such as PROFINET and PROFIBUS are always double-ended. Where low-frequency circuits must share a tray, break the loop with isolation transformers, optocouplers or signal isolators. VFD motor cables, with their high dv/dt PWM edges, require double-ended 360-degree bonding plus EMC glands.
Implementation details decide everything. For 360-degree bonding, unwrap the shield and clamp the full circumference against the metal housing with an EMC gland or metal collar; a pigtails inductance costs more than 20 dB of shielding effectiveness above 1 MHz. For single-ended, bond at the receiver because it is the low-impedance end with a discharge path. A shield floating at both ends is worse than none — accumulated static discharges into inputs and destroys them. Capacitive hybrid earthing (10 to 100 nF to earth) can serve both regimes, provided capacitor voltage rating is at least 250 V and the failure mode is considered.
| Signal type | Bandwidth | Recommended | Earthing point |
|---|---|---|---|
| 4-20 mA analog | DC to tens of Hz | Single-ended | Receiver side (cabinet) |
| Thermocouple / RTD | DC | Single-ended | Receiver side |
| Load-cell signals | DC to tens of Hz | Single-ended | Receiver side |
| Encoder pulses | Tens of kHz to MHz | Double-ended 360-degree | Both ends |
| PROFINET / PROFIBUS | MHz range | Double-ended 360-degree | Both ends |
| VFD motor cable | PWM carrier | Double-ended 360-degree | Both ends, EMC glands |
| Coaxial video | Wideband | Single-ended | Recorder end |
| Low-frequency, shared tray | Low frequency | Single-ended plus isolator | Receiver with optocoupler |
For signal and power cable shielding inside and outside control cabinets. Two sayings cover it: single-ended at low frequency stops loops, double-ended at high frequency stops radiation; and double-ended always 360-degree, single-ended always at the receiver. Never leave a shield floating.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: EMC installation per GB/T 5226.1 and IEC 61800-3; shielding and earthing detail per the GB/T 17626 EMC test series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.