Clearance governs breakdown through air, creepage governs tracking along surfaces — mixing them up produces non-compliant cabinets. This page separates the two, shows the table look-up and calculation steps, and walks a real measurement example.
Definitions. Clearance is the shortest straight-line distance through air between conductive parts, resisting air breakdown; it depends on voltage magnitude, especially transient overvoltage, and needs correction only above 2000 m altitude. Creepage is the shortest distance along the insulation surface, resisting surface flashover and tracking; it depends on RMS working voltage, the material group by CTI (group I at 600 or more, II at 400-600, III at 100-400) and the pollution degree (1-4, with industrial environments typically degree 3). For the same pair of conductors, creepage requirements usually exceed clearance — a surface that is dirty withstands less than clean air does.
Worked example per GB/T 16935.1 (IEC 60664-1), for a 380 V AC system, pollution degree 3, material IIIa: working voltage 250 V to earth (380 V phase-to-phase), overvoltage category III with 4000 V transients. Clearance from the tables: 3.0 mm. Creepage at 250 V, degree 3, material IIIa: 4.0 mm — so phase-to-phase takes the larger value. A practical case: busbar supports measuring 25 mm of air between phases, far above the requirement, yet a dusty, damp insulator surface offering only 12 mm of tracking path can still flash over if the material CTI is poor — hence checking creepage distance per kV (25 mm/kV or better) in wet, dusty plants.
Design verification routine: list every conductor pair (phase-phase, phase-earth, control versus power), assign working voltage and overvoltage category, look up both requirements, and measure the actual distance taking the larger. Four classic errors: counting only straight-line distance and ignoring segmented surface paths around ribs; crediting grooves narrower than 1 mm, which pollution degree 3 bridges; terminal blocks whose rated insulation voltage does not cover the actual circuit; and PCB spacing designed for low voltage but used on high-voltage circuits, where reinforced insulation (roughly double basic) applies on isolated supplies. Accept with calipers and feeler gauges, checking both drawing and physical distances.
| Condition | Clearance | Creepage | Basis |
|---|---|---|---|
| 220 V control, pollution 2, group II | 1.5 mm | 2.0 mm | GB/T 16935.1 |
| 380 V to earth, pollution 3, IIIa | 3.0 mm | 4.0 mm | GB/T 16935.1 |
| 380 V phase-phase, pollution 3 | 3.0 mm or more | 5.0 mm or more | Derived at 250 V earth |
| DC 600 V bus, pollution 3 | 4.0 mm or more | 8.0 mm or more | By working voltage |
| Reinforced insulation | 2x basic | 2x basic | IEC 60664-1 |
| Altitude 2000-5000 m | Factor 1.14-1.48 | No correction | IEC 60664-1 |
| Pollution degree 4 | Vendor derating | Much larger, or potted | IEC 60664-1 |
| PCB high-voltage spacing | By voltage tables | Halved under coating | IEC 60664-3 |
For insulation verification across cabinets, drives, power supplies and terminal blocks. Design to the worst case (pollution 3, low-CTI material) and verify with calipers at acceptance. Remember: air needs clearance, surfaces need creepage, take the larger, and sum surface paths segment by segment.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Insulation coordination per GB/T 16935.1 (IEC 60664-1); PCB insulation per IEC 60664-3; machine electrical context per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.