The most common fault source in a cabinet is not a component but a terminal: one loose screw can burn out a board in half a year. This page explains the heating mechanism, infrared detection, torque standards and the prevention regime.
The chain runs like this: vibration, thermal cycling and copper-aluminium creep raise the joint resistance from microohms to milliohms — a thousand-fold increase. Heating follows P=I²R: on a 100 A circuit, an added milliohm dissipates 10 W continuously at one point, pushing 150-300 C that carbonises insulation and anneals copper until a short or fire. The whole process takes 3 to 12 months and is progressive: mildly warm on infrared, then stained and smelly, then carbonising. Copper-to-aluminium joints without transition terminals are the worst offenders, and vibrating environments loosen terminals 3 to 5 times faster.
Detection and tightening. Infrared thermography every six months on live boards is the best finder, judged as: over 10 K against surrounding conductors gets tracked, over 20 K gets re-torqued, over 40 K gets de-energised immediately — and always at 50 percent load or more, because an unloaded joint shows nothing. Torque standards: M4 about 1.2-1.6 N·m, M5 2-3, M6 4-6, M8 8-12, M10 16-22 N·m with a preset torque driver, never by feel; prepare the joint faces by removing oxide and applying conductive paste; respect terminal wire-count limits. Live tightening is banned in principle — schedule an outage; if unavoidable, insulated tools plus a watcher.
Prevention has four parts: a full torque check three months after commissioning (the settling-in period is when looseness peaks), then yearly; anti-loosening measures (spring washers, thread locker, anti-vibration terminals) in vibrating areas; wireless temperature sensors on critical joints with over-temperature alarms — excellent return on key circuits; and a formalised biannual infrared round with trend records. After a heat fault, never just re-tighten: the carbonised, annealed contact face has irreversible resistance, so replace the terminal and conductor end, re-crimp, and re-verify the temperature under load.
| Stage | Standard / method | Value | Notes |
|---|---|---|---|
| Infrared round | Twice yearly, ≥50 percent load | 10 K track, 20 K act | Trend records |
| Torque M6 | Preset torque driver | 4-6 N·m | Never by feel |
| Torque M8 | Preset torque driver | 8-12 N·m | Spring washer |
| Cu-Al joints | Transition terminals | Direct joint forbidden | Creep hotspot |
| First tightening | 3 months after startup | Full torque survey | Looseness peak |
| Temperature monitoring | Wireless sensors | Over-temp alarm | Critical circuits |
| Post-fault handling | Replace the contact face | Carbonised means replaced | Re-torque alone relapses |
| Vibration areas | Anti-loosening hardware | Washer plus thread locker | Loosens 3-5x faster |
For terminal and busbar maintenance across LV boards, control cabinets and distribution boxes. The insight: loose-joint heating is a months-long chronic disease, and the trio of infrared rounds, torque-controlled tightening and first-tightening at three months drives it to zero. A heat-damaged joint gets a new contact face, not another twist of the wrist.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Connections and terminations per GB/T 5226.1 (IEC 60204-1) chapter 13 and the GB/T 7251 assembly series; infrared diagnostics per DL/T 664. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.