Wire too thin to crimp solid, too thick to fit, or two conductors stuffed into a single-position terminal — the heat faults follow. This page covers the matching rules, the repair procedure and the retrofit approach.
Three mismatch patterns. Undersized wire in the terminal: a 0.75 mm² core in a 2.5 mm² barrel is never gripped solid, and the joint heats within months. Oversized wire: forcing it damages strands or leaves the crimp loose, with the same heating plus a weakened, break-prone core. Multiple conductors in a single-position terminal: uneven crimping force doubles both loosening and heating risk — parallel connections need extended-barrel twin terminals or a distribution block. The failure chain mirrors loose terminals: rising contact resistance, I²R heating, carbonised insulation, short and fire. On the thermal image the fault is a single bright dot at the crimp, not along the wire.
Matching rules: select wire within the marked range on the terminal (0.75-2.5 mm², for instance), never beyond it; use twin-barrel terminals or busbars for parallel runs; choose ferrules by cross-section and screw size (E25-8 means 2.5 mm² wire for an M8 screw); and always fit ferrules to stranded wire — bare strands squashed directly into a terminal splay and half the copper never makes contact. Repair flow for a hot joint: de-energise and verify; replace the terminal and re-crimp with the matching die, pull-testing samples; replace any wire whose insulation has cooked; re-torque every other terminal on the same circuit, since one hot joint usually indicates a batch workmanship problem; then re-measure at 50 percent load and require a stable 48 hours before signing off.
Prevention: size terminals with 1.5 times current margin at design, verify wire ampacity and voltage drop, and print cross-sections and terminal types on the drawings so nobody guesses on the floor. In installation, match dies to terminals, inspect crimps visually (indent centred, 1-2 mm of strand showing) and pull-test power circuits. Retrofitting older boards: replace stuffed multi-wire terminals with distribution blocks or double-deck terminals, and re-crimp mismatched wiring in batches followed by an infrared re-check. Crimping is a trained skill — certify operators and accept by pull test and visual.
| Item | Rule | Typical value | If violated |
|---|---|---|---|
| Cross-section match | Within the marked range | E.g. 0.75-2.5 mm² | Loose crimp, heating |
| Parallel wires | Twin barrel or busbar | Never two in a single position | Double the risk |
| Ferrule selection | By section and screw size | E25-8: 2.5 mm² on M8 | Poor contact |
| Stranded wire | Ferrule mandatory | No bare strands direct | Splaying and breakage |
| Crimp die | Matched to terminal | Correct section die | Under- or over-crimp |
| Visual check | Centred indent, 1-2 mm show | Every crimp | Defects shipped |
| Post-repair check | Measure at 50 percent load | Stable for 48 hours | Relapse risk |
| Design margin | 1.5x current or more | Per ampacity tables | Chronic overheating |
For wiring design and repair in control cabinets, power circuits and distribution boxes. Check three things every time: section range, wire count limit, ferrule type. Heat repairs mean a new crimp plus a batch-wide re-torque, and retrofits cure multi-wire problems with busbars or double-deck terminals.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Terminations per GB/T 5226.1 (IEC 60204-1) chapter 13; ampacity per GB/T 16895 wiring tables; ferrule standards per GB/T 14315 and related. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.