Fitting everything in is not the same as fitting it in right. Drive beside PLC, mixed 24V and 230V terminals, and uncalculated heat - layout faults manufacture years of trouble. Here are the zoning, cooling and routing rules.
Three separations. Low versus high energy: PLC, HMI and signal modules on one side; breakers, contactors and relays on the other, with 10cm of clearance or a metal divider between; the drive and its filters get their own zone, at least 30cm from analogue modules. Voltage separation: AC 380/230 terminals and DC 24 terminals on different rows with colour coding - mixed rows are how modules get shorted during maintenance. Heat separation: transformers, drives and braking resistors sit high or in their own air path, so hot air rises past the electronics, not through it. Draw the zoning sketch at design stage and build to it.
Cooling is calculated, not felt. Sum the losses - PLC 20~50W, a drive roughly 3~5 percent of its rating, transformer plus coil losses - against natural dissipation of about 5~10W per square metre of cabinet surface per 10K rise. A 7.5kW drive already needs forced ventilation; 22kW and above starts talking air conditioning. Target: below 40C long-term inside, below 55C at the components; every 10C over rating halves electronic life. Routing: power, control and signal wiring in separate ducts or with dividers, drive output cable run alone and shielded 360 degrees, an earthing busbar of 16mm2 or more with short local taps, 20 percent spare terminals, and printed wire numbers matching the drawing. Acceptance checks: zoning as drawn, one-hour full-load temperature check, earth continuity under 0.1 ohm, and real spare space for future modules.
| Zone or item | Requirement | Typical value | If violated |
|---|---|---|---|
| Low/high energy separation | 10cm gap or metal divider | PLC side apart from power side | Interference, random faults |
| Drive placement | Own zone near the vent | 30cm from analogue modules | Analogue glitches, phantom alarms |
| Heat sources | High up or own air path | Hot air bypasses the PLC | CPU derating and crashes |
| Cabinet temperature | Below 40C long-term | 10C over rating halves life | Batch ageing of electronics |
| Terminal rows by voltage | AC and DC separated, colour coded | 20 percent spare | Cross connection burns modules |
Low left, high right, heat up, signals away from noise, one earthing busbar. Accept the cabinet on three checks: zoning sketch, full-load temperature rise, measured earth continuity. Retrofitting elements later needs a fresh heat and zoning calculation - no squeezing into gaps.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Temperature rise and arrangement for low-voltage assemblies per GB/T 7251.1 (IEC 61439-1), installation and wiring per GB/T 5226.1 clauses 4 and 13. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.