E.THT on a Mitsubishi drive is rarely the drive running hot - it is the electronic thermal model tripping for the motor. Know its cousin E.FIN, set Pr.9 from the motor, and the alarm becomes a useful signal.
E.THT is the electronic overcurrent protection: the drive models motor heating from the set electronic thermal current and trips on the inverse-time characteristic when current stays above it - roughly one to two minutes at 120 percent and tens of seconds at 150 percent, scaled to the Pr.9 setting. E.FIN is the heatsink overtemperature; separating the two decides the whole direction - E.THT sends you to load and settings, E.FIN to fans and ambient. The trap: Pr.9 ships at the drive rated current, so a small motor on a big drive has no protection until you set it to the motor nameplate.
Set it in three moves: Pr.9 to the motor rated current; the thermal characteristic to standard or constant-torque inverter-duty motor as the load demands - inverter-duty motors with independent cooling differ from self-cooled ones; and for long low-speed running below 20Hz with a self-cooled motor, discount the setting by 10~20 percent or fit a separate fan. Verify with a full-load hour run: frame temperature inside the insulation class and no alarm. When it trips: reset test - an immediate retrip is a hard overload, a delayed one is creeping; clamp the three phases against Pr.9, check unbalance above 10 percent, confirm nobody enlarged Pr.9, inspect for stalling and bearing drag, and log the current every trip - three points make a trend.
| Check | Method | Criterion | Action |
|---|---|---|---|
| Pr.9 setting | Against motor nameplate | Matches | Correct if set to drive rating |
| Output current | Clamp all three phases | Below setting | Above: chase the load |
| Phase balance | Compare three currents | Under 10 percent | Check for lost phase, wiring |
| Running frequency | Long-term frequency log | Above 20Hz | Below: add forced cooling |
| Motor temperature | Infrared on the frame | Within insulation class | Over: cooling and load review |
First tell E.THT from E.FIN, then the setting, then the current, then the low-speed duty. The electronic thermal is the motor bodyguard - set it small and it nags, set it big and it abandons the motor. Nameplate plus a loaded heat run, both mandatory.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive protection per GB/T 12668.2 (IEC 61800-2), motor rating and temperature rise per GB/T 755, settings per the Mitsubishi manual. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.