A motor that trips the instant it starts may be perfectly fine - the protection may be wrong. Direct-on-line starting draws five to seven times rated current by physics, and the diagnosis starts by separating protection issues from motor faults.
DOL starting runs at maximum slip, so the rotor sees the highest induced current: 5~7 times rated for 0.5~2 seconds depending on load inertia. Trips split into two families: thermal, where the starting time outlasts what the bi-metal tolerates, and magnetic, where the inrush peak enters the instantaneous band - 5~10 times rated for a C curve, 10~20 for D. Large-inertia loads on C-curve breakers trip almost every start, which is a selection problem, not a broken motor.
Set the thermal relay at 1.0~1.05 times nameplate current (1.05~1.15 for heavy starts or hot rooms) and match its trip class to the starting time: class 10 for starts under 10s, class 20 or 30 for longer runs. To diagnose, first note which device tripped; then with power off, bar the rotor by hand - a seized bearing or stator rub feels heavy - and megger the insulation. Clamp the starting peak: above 8 times rated with a dull droning sound and swinging phase currents suggests broken rotor bars. Finally start unloaded: if that succeeds, chase the load, not the motor.
| Pattern | Points to | Verification | Action |
|---|---|---|---|
| Instant trip at switch-on | Instantaneous band or short | Peak clamp, insulation test | D curve or clear fault |
| Trip late in the run-up | Long start or tight setting | Trip class vs start time | Class 20/30 or soft start |
| Heavy to bar by hand | Seized bearing or rub | Open and inspect | Replace bearing |
| Above 8x current, dull sound | Broken rotor bars | Compare phase currents | Send for repair |
| Starts fine uncoupled | Load or starting method | Run motor alone | Fix load, soft start |
The rule: separate thermal from magnetic, unloaded from loaded, then look at the inrush multiple. Never silence trips by winding the thermal relay up past 1.15 times rated - that removes overload protection entirely.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Protective coordination per GB/T 14048.2 and GB/T 14048.4 (IEC 60947-4-1 trip classes), machinery safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.