Why 4-20mA loops drift, and how to pin the blame

A drifting analogue loop upsets the process long before it fails outright. Six families of causes, three verification moves, and the numbers that separate meter from wire from transmitter.

1. How it works

Drift has six sources: ground loops, where a potential difference between the two ends adds interfering current; loop resistance beyond what the transmitter can drive (commonly 300~500 ohms at DC24V); electromagnetic coupling from cables run beside power lines or near drives; oxidised terminals drifting contact resistance; the transmitter itself - temperature drift, zero shift, aged diaphragm; and a noisy or wandering supply.

2. Practice and pitfalls

Verify with three moves. Put a milliamp meter in series: if the meter is steady while the screen drifts, the fault is in the acquisition side; if both drift, look at the loop. Lift the shield at both ends as a ground-loop experiment. Inject 4, 12 and 20mA from a calibrator at the input: a good acquisition side moves the blame to the transmitter or the wiring. Working numbers: measured loop resistance below the datasheet limit, drift beyond 0.5 percent of span worth fixing, transmitter calibration within 0.2 percent against a standard source. Nine times out of ten the fault is wiring, shielding or earthing - not the transmitter.

3. 4-20mA drift quick table

Drift signaturePoints toVerificationAction
Slow drift, tracks temperatureTransmitter drift, aged cellCalibrate against sourceCalibrate or replace
Jumps when drives startEMI couplingCompare with equipment offShielded pair, separation
Several loops affect each otherGround loop currentShield earthing experimentSingle-end earth or isolator
Reads low, worse under loadLoop resistance too highMeasure total loop ohmsClean terminals, reduce burden
Screen and field meter disagreeScaling or configurationInject known currentCheck range and setup

4. Notes

The series milliamp meter is the watershed: it splits meter from wire. Annual loop care is three jobs - terminal torque, shield earthing, sampled calibration - and never change the transmitter before the loop is proven innocent.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Transmitter performance per GB/T 17614 (IEC 60770), equipotential bonding and signal earthing per GB/T 5226.1 clause 8. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Earthing the shield at both ends: ground potential difference becomes a circulating current and drift worsens - earth at the control side only
② Breaking the loop carelessly to insert the meter: an open moment alarms the process - use a clamp milliamp meter or bridge first
③ Swapping the transmitter for drift: wiring and earthing faults survive the swap - assign blame with a current source first

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.