A drifting analogue loop upsets the process long before it fails outright. Six families of causes, three verification moves, and the numbers that separate meter from wire from transmitter.
Drift has six sources: ground loops, where a potential difference between the two ends adds interfering current; loop resistance beyond what the transmitter can drive (commonly 300~500 ohms at DC24V); electromagnetic coupling from cables run beside power lines or near drives; oxidised terminals drifting contact resistance; the transmitter itself - temperature drift, zero shift, aged diaphragm; and a noisy or wandering supply.
Verify with three moves. Put a milliamp meter in series: if the meter is steady while the screen drifts, the fault is in the acquisition side; if both drift, look at the loop. Lift the shield at both ends as a ground-loop experiment. Inject 4, 12 and 20mA from a calibrator at the input: a good acquisition side moves the blame to the transmitter or the wiring. Working numbers: measured loop resistance below the datasheet limit, drift beyond 0.5 percent of span worth fixing, transmitter calibration within 0.2 percent against a standard source. Nine times out of ten the fault is wiring, shielding or earthing - not the transmitter.
| Drift signature | Points to | Verification | Action |
|---|---|---|---|
| Slow drift, tracks temperature | Transmitter drift, aged cell | Calibrate against source | Calibrate or replace |
| Jumps when drives start | EMI coupling | Compare with equipment off | Shielded pair, separation |
| Several loops affect each other | Ground loop current | Shield earthing experiment | Single-end earth or isolator |
| Reads low, worse under load | Loop resistance too high | Measure total loop ohms | Clean terminals, reduce burden |
| Screen and field meter disagree | Scaling or configuration | Inject known current | Check range and setup |
The series milliamp meter is the watershed: it splits meter from wire. Annual loop care is three jobs - terminal torque, shield earthing, sampled calibration - and never change the transmitter before the loop is proven innocent.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Transmitter performance per GB/T 17614 (IEC 60770), equipotential bonding and signal earthing per GB/T 5226.1 clause 8. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.