Too fast and the drive trips on every start; too slow and the modules burn. Instantaneous, software and stall-prevention layers - and how acceleration times shape them all.
Overcurrent protection works in three layers. Hardware instantaneous detection watches the IGBTs with microsecond response - fixed, not adjustable, and a short circuit always lands there. Software overcurrent trips when output current exceeds a threshold, typically 150~200 percent of rating, for longer than a set time, commonly 0.5~2s. Stall prevention is the preventive layer: during accel or decel, when current reaches its limit the ramp pauses instead of overshooting. The user tunes the lower two; the logic is stall prevention first, software overcurrent as the net, hardware as the last resort.
Tune in order. Acceleration first: estimate from inertia, start long - say 30s - and shorten toward the alarm edge, then back off 20 percent. Then the overcurrent threshold and time: normal operating peaks belong below the 150 percent threshold, and the delay must tolerate normal inrush (well under half a second) while still catching sustained overload; set stall-prevention limit at 90~95 percent of the overcurrent threshold so prevention acts first. The classic mistakes: short accel times leaning on stall prevention, hammering the modules on every start; and a zero-second software trip that fires on every healthy inrush. Verify with recorded start curves - peaks inside 80 percent of threshold - ten consecutive loaded starts without alarm, and where the process allows, a sustained-overcurrent test proving the timer acts as set.
| Layer | Typical setting | Role | Note |
|---|---|---|---|
| Hardware instantaneous | Fixed | Protects the IGBTs | Shorts always land here - never probe it |
| Software overcurrent | 150~200 percent, 0.5~2s | Overload net | Tolerate inrush, not overload |
| Stall prevention | 90~95 percent of threshold | Accel/decel guard | Riding the limit means accel too short |
| Acceleration time | Shrink toward the edge | Limits start current | Back off 20 percent after alarms |
| Deceleration time | By regen capability | Prevents overvoltage | Coordinate with braking |
Times first, threshold second, prevention ahead of trip, hardware as the last wall. Recorded start curves beat guesswork, and the action test belongs in a process window with results filed for the annual recheck.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive protection and testing per GB/T 12668.2 (IEC 61800-2), protection coordination per GB/T 5226.1 clause 7. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.