Standard induction motors were designed for sinusoidal supplies, not for PWM pulse trains. This page covers the four practical risks of running them on a drive: insulation stress, shaft currents, low-speed cooling loss and noise, with concrete thresholds and fixes.
PWM output pulses with dU/dt in the kV per microsecond range stress the winding insulation through reflected-wave voltage peaks that can reach 1.5 to 2 times the DC bus. For 400V motors with cable runs beyond 50m, fit an output reactor or dv/dt filter; beyond 150m it is effectively mandatory. Motors built for inverter duty with reinforced insulation are the better long-term choice.
High-frequency common-mode voltage induces a shaft voltage that discharges through the bearing oil film, leaving fluting patterns that destroy bearings within months. Fit an insulated bearing on the non-drive end or an shaft grounding brush when shaft voltage exceeds about 300mV peak, typically on motors above 55kW. Below 20Hz, shaft-mounted cooling fans lose most of their effect, so derate to about 70 percent or add a separate forced-air fan.
| Risk | Symptom | Threshold | Countermeasure |
|---|---|---|---|
| Insulation aging | Partial discharge, turn faults | Noticeable beyond 50m cable | Output reactor or dv/dt filter |
| Bearing currents | Fluting, bearing noise | Shaft voltage above 300mV | Insulated bearing or grounding brush |
| Low-speed overheating | Winding overtemperature | Sustained below 20Hz | Forced fan or derate to 70 percent |
| Audible noise | Magnetic whine | Carrier below 4kHz | Raise carrier to 8~10kHz |
| Vibration | Resonance band shaking | Common at 5~15Hz | Set jump frequencies to skip the band |
When retrofitting an old machine, check cable length first, then bearing and power level, then the lowest process frequency. Pass all three checks and a standard motor can run on a drive for a decade.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Winding stress for converter-fed motors is covered by IEC 60034-25 and machine safety requirements by IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.