Ramp handling between multi-speed steps on a VFD

Multi-speed running involves more than presetting a few frequencies: the ramp handling between steps decides whether the motor glides or lurches. This page covers shared versus per-step ramps, the transition logic and the interlock details that keep terminals honest.

1. How it works

Most drives offer either one shared ramp pair for all steps or independent ramps per step in program-run mode. Per-step ramps matter when inertia behaviour differs by direction: braking hard from high to low speed in one second while climbing back in eight. With terminal-based multi-speed selection the drive picks up the new target and ramps there using the active ramp times, so rapid back-and-forth terminal toggling simply stacks recalculated ramps and current ripple grows.

2. Practice and pitfalls

Practical frame: inter-step acceleration of 3~10 seconds by inertia, deceleration of 3~5 seconds with the bus voltage verified, and step differences kept within about 30Hz because a 40Hz jump with a one-second ramp overloads both current and regeneration. In PLC logic, add a 100~200ms interlock between terminal changes so the binary step code never passes through an illegal combination, and prefer analogue or bus setpoints where stepless transitions are possible.

3. Multi-speed setting quick reference

ItemSuggested valueConsequence if wrongHow to check
Inter-step accel3~10sCurrent hits limit, OC tripWatch accel current trace
Inter-step decel3~5sBus overvoltageWatch decel bus voltage
Max step gapAbout 30Hz or lessBoth current and regen spikesCompute adjacent step delta
Terminal interlock100~200ms delayIllegal code from contact bounceInterlock in PLC program
Dwell per stepBy process, over 1sStraight cuts with no rampCheck program-mode times

4. Notes

Commission in order: test each step alone for frequency and direction, then run the loop while watching current spikes at every transition, and lengthen the corresponding ramp whenever a spike exceeds 1.5 times rated.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive functions per IEC 61800-2 / GB/T 12668.501, interlocks and safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Cutting a 40Hz step gap with a one-second ramp: current pins the limit uphill and the bus pins overvoltage downhill, trips on both ends
② Switching the step code without a PLC interlock: contact bounce creates an illegal combination and the frequency jumps mid-cut, scrapping the workpiece
③ Setting dwell time to zero in program mode: steps cut with no ramp, shock travels into the gearbox and teeth break within half a year

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.