Multi-speed running involves more than presetting a few frequencies: the ramp handling between steps decides whether the motor glides or lurches. This page covers shared versus per-step ramps, the transition logic and the interlock details that keep terminals honest.
Most drives offer either one shared ramp pair for all steps or independent ramps per step in program-run mode. Per-step ramps matter when inertia behaviour differs by direction: braking hard from high to low speed in one second while climbing back in eight. With terminal-based multi-speed selection the drive picks up the new target and ramps there using the active ramp times, so rapid back-and-forth terminal toggling simply stacks recalculated ramps and current ripple grows.
Practical frame: inter-step acceleration of 3~10 seconds by inertia, deceleration of 3~5 seconds with the bus voltage verified, and step differences kept within about 30Hz because a 40Hz jump with a one-second ramp overloads both current and regeneration. In PLC logic, add a 100~200ms interlock between terminal changes so the binary step code never passes through an illegal combination, and prefer analogue or bus setpoints where stepless transitions are possible.
| Item | Suggested value | Consequence if wrong | How to check |
|---|---|---|---|
| Inter-step accel | 3~10s | Current hits limit, OC trip | Watch accel current trace |
| Inter-step decel | 3~5s | Bus overvoltage | Watch decel bus voltage |
| Max step gap | About 30Hz or less | Both current and regen spikes | Compute adjacent step delta |
| Terminal interlock | 100~200ms delay | Illegal code from contact bounce | Interlock in PLC program |
| Dwell per step | By process, over 1s | Straight cuts with no ramp | Check program-mode times |
Commission in order: test each step alone for frequency and direction, then run the loop while watching current spikes at every transition, and lengthen the corresponding ramp whenever a spike exceeds 1.5 times rated.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive functions per IEC 61800-2 / GB/T 12668.501, interlocks and safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.