A valve terminal concentrates dozens of solenoids; one power design mistake shakes everything. This page covers supply architecture, common terminals, bus wiring and earthing.
Two supply tiers: solenoid power at 24 V, sized from coil total times 1.5, for instance 20 coils at 2.5 W need about 3 A, and separate sensor supply with per-circuit fusing. Keeping the tiers apart stops valve switching transients from polluting sensor power. Wiring: 0.75 mm² minimum for a 3 A branch, 1.5 mm² trunk. Per-valve fusing or terminals with individual protection prevents one shorted coil from taking down the island. Ripple below 5 percent, power supply within 5 m.
Common-terminal wiring: PNP (positive common) dominates; the valve terminal type must match the PLC output type exactly, since mixing leaves coils dead or permanently energised. Bus terminals such as PROFINET or EtherCAT replace per-valve wiring with two power wires and one bus cable; import the GSDML device description and map outputs by position. Earth the mounting plate directly to PE; shield signal lines single-ended.
Power up sensor supply first, then valve power, to avoid unwanted motion. Bus diagnostics show per-valve operation counts and coil states, making sticking and breakage obvious. Typical faults: one dead valve, check diagnostics then coil resistance, about 300 to 500 ohms; whole-island jitter, check ripple and earthing; random resets, check bus termination and shielding. Tape the supply diagram and output map inside the cabinet.
| Item | Recommended | Wrong |
|---|---|---|
| Supply grouping | Valve and sensor supplies separate | Shared, mutual interference |
| Sizing | Coil total times 1.5 | Bare nameplate total |
| Wire gauge | 1.5 mm² trunk | 0.5 mm² running hot |
| Protection | Per-valve fuse | One fuse for all |
| Bus setup | Import device description | Scan without files |
| Earthing | Plate direct to PE | Floating |
Prefer terminals with per-valve diagnostics; 10 percent extra pays back in fault-finding within months. Archive the supply diagram, output map and DIP states with the cabinet so handovers never rely on memory.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring and terminals follow GB/T 5226.1; valve terminals and bus interfaces reference the IEC 61131 and IEC 61784 profiles. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.