Variable frequency drives are the largest harmonic source in most plants, and the 5th and 7th harmonics injected by six-pulse rectifiers overheat transformers, swell capacitor cans and upset instruments. This page walks the origin, the compliance limits and a cost-ranked ladder of mitigation measures.
A six-pulse bridge draws pulsating current that appears on the grid as harmonics of order 6k plus or minus one. Measured fifth-harmonic current often reaches 30 to 50 percent of the fundamental, and an unrated drive at full load can show current THD above 80 percent. The damage is visible: transformers and cables heat from skin effect, so at 15 percent harmonic content the rating loses about a fifth; power-factor capacitors resonate with the system inductance near a characteristic order and swell or burst; triplen harmonics sum in the neutral to 1.7 times phase current, overloading a neutral sized to the phase conductor.
Judge compliance against GB/T 14549, which limits voltage THD to 5 percent on 380V systems. Measure with a portable power-quality analyser at the transformer LV main board over 24 hours and focus on peak-hour figures. Quick field checks: bulged capacitors and frequent fuse blows point to resonance; a transformer running hotter than its twins at the same load points to harmonics; a humming or overheating neutral joint confirms triplen build-up. Measure at the point of common coupling, not at one drive.
The mitigation ladder in cost order: first, detune every capacitor bank with 7 percent reactors, a few yuan per kvar; second, fit DC-link or line reactors at 3 to 5 percent impedance per drive, cutting current THD from 80 to about 35 percent; third, 12-pulse or PWM (AFE) rectifiers for new high-power projects down to 5 percent; fourth, a central passive filter bank or active filter sized at 10 to 20 percent of transformer rating. Solve the resonance before buying an active filter, or the money is wasted.
| Measure | Current THD typical | Relative cost | Best suited for | Caution |
|---|---|---|---|---|
| No measures at all | 80%~120% | Zero | Forbidden on new projects | All hazards stacked |
| Line or DC reactor | 30%~40% | Low | Mandatory per drive | Check torque at 2~3% drop |
| Capacitors with 7% reactors | System dependent | Low | Standard on PFC banks | Resonance moved to ~3.8th |
| 12-pulse rectifier | 10%~15% | Medium | New high-power units | Needs phase-shift transformer |
| PWM rectifier (AFE) | 3%~5% | High | Regeneration plus clean power | About twice the price |
| Active filter (APF) | <5% after compensation | Medium-high | Central bus treatment | Size by harmonic current |
Solve resonance first, then add reactors per drive, and only then consider central filtering; re-measure voltage THD after any retrofit and inspect capacitor banks quarterly for bulging and noise.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Limits per GB/T 14549; equipment safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.