Old freight elevators run two-speed motors with rough landings and heavy starting current. This page walks a real retrofit: the scheme, the untouched safety circuit, the tuning details and the measured before-and-after data.
A 2-tonne freight elevator with pole-changing two-speed control landed within 30~50mm and started at four times rated current. The retrofit: an 11kW inverter-duty traction motor, a 15kW G-frame drive with 20 percent current margin, encoder closed loop, and the brake interlocked from the drive zero-speed signal. Result: landing accuracy within plus or minus 5mm, starting current 1.2 times rated, and about 20 percent annual energy saving from removing the inefficient low-speed winding.
The safety principle is absolute: safety gear, governor, upward over-speed protection and door locks stay untouched, only the drive control changes. Drive faults feed the elevator stop logic, cutting output and setting the brake, and inspection mode stays below 0.63m/s. Commissioning adds pre-torque compensation calibrated by load tests and a 0.2~0.3m/s creeping segment for levelling. Acceptance ran 20 full trips loaded and empty, all landings within 5mm, noise down from 85dB to 68dB, with parameter backup, tuning records and the inspection report handed over.
| Item | Before | After | Improvement |
|---|---|---|---|
| Landing accuracy | 30~50mm | Within ±5mm | Six to ten times better |
| Starting current | 4 times rated | 1.2 times rated | Down 70 percent |
| Annual energy | Baseline | About 20 percent less | Inefficient winding removed |
| Noise | About 85dB | About 68dB | Down 17dB |
| Creeping speed | None | 0.2~0.3m/s | New levelling segment |
| Downtime | None | 5 days | Including inspection |
Freight elevators are regulated equipment: confirm local rules, use a licensed contractor, keep the safety circuit intact with records. Treat the case numbers as feasibility reference, not as copy-paste settings.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Elevator inspection and modification follow GB/T 10058 with machine electrical safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.