Torque boost has a hard physical ceiling, and counting on it to paper over a sizing error is a trap. This page sets the boundary of what boost recovers, how much margin sizing should carry, and when a frame up is the only answer.
Boost compensates the stator resistance drop at low frequency and restores the flux that should have been there, lifting 5Hz torque from roughly half back to about rated. Sustained 150 percent output at low speed on plain V/F is out of reach because the current limit governs. The real ledger for starting torque is the overload rating: 150 percent for one minute on heavy-duty G frames, 120 percent on light-duty P frames.
Sizing arithmetic: pick drive rated current at 1.1~1.15 times the motor for constant torque, another 10 percent margin for frequent 150 percent starts, 1.0~1.05 times for fans and pumps on P frames, and add 10~20 percent for continuous running below 20Hz where self-cooling fades. Always size by nameplate current, not power: an 11kW six-pole motor draws about 25A against 22A for a four-pole, and current is what trips. When a machine is already installed and weak at low speed, check boost and curve type first, then accept that a bigger frame or vector control is the honest fix.
| Condition | Sizing basis | Margin | Note |
|---|---|---|---|
| Fans and pumps, P frame | 1.0~1.05 times motor current | None needed | 120 percent overload suffices |
| General constant torque, G frame | 1.1~1.15 times motor current | 10 percent | 150 percent for 1 minute |
| Frequent heavy starts | G frame one size up | Extra 10 percent | Prefer vector control |
| Continuous below 20Hz | On top of G frame | Extra 10~20 percent | Or add a forced-air fan |
| Six-pole and slower motors | Always by rated current | Never less | Higher current at same power |
Anchor every calculation on the motor nameplate current rather than power. For installed machines that lack low-speed torque, verify boost and curve type, then upgrade the frame if the shortfall persists.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive ratings and overload definitions per IEC 61800-2 / GB/T 12668.501, machine safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.