Put several drives on one bus and a duplicated station number, mismatched baud rate or wrong parity paralyzes the whole line. This page gives the setting rules, the addressing plan and the troubleshooting order for drive networks.
The three elements are baud rate, frame format and protocol. Modbus RTU typically runs 9600 or 19200bps with 8 data bits, even parity and one stop bit; Profibus and Proconet are configured from the master, leaving only the station address to set on the slave. Every slave must share the same baud rate and format, and every station number must be unique. New drives often ship with station 1, so two freshly installed units clash immediately: plan addresses from the drawing, set baud rates, then wire and power up.
Plan addresses by area with headroom, keep the drawing, parameter sheet and cabinet labels in agreement, and archive the register map of the first commissioned drive as the template. When the bus is dead, check in order: master counters rising on transmit but not receive points to wiring or slaves; reversed A and B lines on RS485 are the most common fault, daisy-chain topology with 120 ohm terminators at both ends is mandatory, and star branches cause reflections. More than half of fieldbus faults are polarity and terminators, so check wiring before suspecting devices.
| Parameter | Modbus RTU typical | Profibus or Profinet | Consistency rule |
|---|---|---|---|
| Baud rate | 9600 or 19200bps | Set by master configuration | Same across the network |
| Frame format | 8E1 or 8N1 | Defined by protocol stack | Same across the network |
| Station number | Self-assigned 1~247 | DIP switch 1~125 | Unique across the network |
| Register map | Brand specific | Defined by GSD file | Archive after first unit |
| Terminators | 120 ohm both ends | 120 ohm both ends | Always at both ends |
Discipline: plan on paper before powering up, cross-check station, baud and parity, wire daisy-chain with terminators, commission one slave at a time, and run a 24-hour error counter before acceptance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Serial link standards per GB/T 19582 (Modbus) and fieldbus per IEC 61158, electrical safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.