A seven-year-old drive that starts tripping on overload with the same motor and load is usually failing inside itself. This page ranks seven causes, from clogged heatsinks to aged bus capacitors and drifted parameters, each with a field test and a repair cost, ending in a priority table.
Over half of derating trips are thermal. Dust, swarf and oil mist blanket the heatsink and choke the airflow, and a 30 percent cooling loss is enough to trigger derating. Cooling fans with ball bearings are rated 30 to 40 thousand hours, so round-the-clock service exhausts them in three to four years, with airflow falling in proportion; a replacement fan costs tens to a few hundred yuan, yet some service shops sell a whole new drive instead. Verify with a check of fan speed and airflow, then an IR thermometer across the heatsink: a healthy inlet-to-outlet rise is 8 to 15 degrees Celsius, and a small rise means choked or short-circuited airflow. Above 40 degrees ambient the rating drops a further 1 to 2 percent per degree, so an unconditioned switchroom in summer can leave only 70 percent capacity.
Bus electrolytic capacitors age exponentially with temperature: at 65 degrees their life is a fraction of the rated 2000 hours at 105, and after 8 to 10 years capacitance falls and ESR rises, showing as deeper bus sag under load, bigger ripple, frequent undervoltage trips and eventually rectifier stress. Compare no-load and full-load bus voltage, listen for HF whistle, and measure capacitance; below 80 percent of nominal the bank should be replaced as a complete matched set, since mixing old and new makes the good capacitors carry extra ripple and fail faster. A capacitor swap runs a quarter to a third of a new drive, well worth it with in-house electricians.
Then check the cheaper items: parameters drifted or overwritten, compare with the backup; current-sensing drift that over-reads by 10 to 20 percent, cross-check with a clamp meter and investigate above 5 percent discrepancy; IGBT ageing with rising saturation voltage, visible as higher module temperature on an IR camera against a new unit; and load-side changes, longer cables or a bigger motor, confirmed by clamping actual current against nameplate. Work the priority table: blow out and re-fan first, parameters second, capacitance and sensing third, and only then consider replacing the unit.
| Check item | How to judge | Cost | Likelihood | Remedy |
|---|---|---|---|---|
| Heatsink clogged | In-out temp rise below 8C | Zero (blow out) | High | Compressed air cleaning |
| Fan worn out | Slow speed or noise | Low | High | Replace with same model |
| High ambient | Cabinet above 40C | Medium | Medium | Cooling or derate |
| Bus capacitors aged | Capacitance below 80% | Medium | Medium, past 8 years | Matched set replacement |
| Parameters altered | Compare with backup | Zero | Medium | Restore backup |
| Current sensing drift | Clamp meter gap above 5% | Medium | Low | Calibrate or swap board |
| IGBT degraded | Module runs hot | High | Low | Module or unit change |
Preventive maintenance every two years for drives past seven: blow out, re-fan, measure capacitance, re-torque terminals, IR survey; log it per unit, and never reset an overload trip twice without stopping to investigate.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance per GB/T 12668.501 / IEC 61800-5-1; equipment safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.