Why an ageing VFD loses its load capacity

A seven-year-old drive that starts tripping on overload with the same motor and load is usually failing inside itself. This page ranks seven causes, from clogged heatsinks to aged bus capacitors and drifted parameters, each with a field test and a repair cost, ending in a priority table.

1. How it works

Over half of derating trips are thermal. Dust, swarf and oil mist blanket the heatsink and choke the airflow, and a 30 percent cooling loss is enough to trigger derating. Cooling fans with ball bearings are rated 30 to 40 thousand hours, so round-the-clock service exhausts them in three to four years, with airflow falling in proportion; a replacement fan costs tens to a few hundred yuan, yet some service shops sell a whole new drive instead. Verify with a check of fan speed and airflow, then an IR thermometer across the heatsink: a healthy inlet-to-outlet rise is 8 to 15 degrees Celsius, and a small rise means choked or short-circuited airflow. Above 40 degrees ambient the rating drops a further 1 to 2 percent per degree, so an unconditioned switchroom in summer can leave only 70 percent capacity.

2. Numbers and practice

Bus electrolytic capacitors age exponentially with temperature: at 65 degrees their life is a fraction of the rated 2000 hours at 105, and after 8 to 10 years capacitance falls and ESR rises, showing as deeper bus sag under load, bigger ripple, frequent undervoltage trips and eventually rectifier stress. Compare no-load and full-load bus voltage, listen for HF whistle, and measure capacitance; below 80 percent of nominal the bank should be replaced as a complete matched set, since mixing old and new makes the good capacitors carry extra ripple and fail faster. A capacitor swap runs a quarter to a third of a new drive, well worth it with in-house electricians.

3. Pitfalls and fixes

Then check the cheaper items: parameters drifted or overwritten, compare with the backup; current-sensing drift that over-reads by 10 to 20 percent, cross-check with a clamp meter and investigate above 5 percent discrepancy; IGBT ageing with rising saturation voltage, visible as higher module temperature on an IR camera against a new unit; and load-side changes, longer cables or a bigger motor, confirmed by clamping actual current against nameplate. Work the priority table: blow out and re-fan first, parameters second, capacitance and sensing third, and only then consider replacing the unit.

4. Troubleshooting priority for lost load capacity

Check itemHow to judgeCostLikelihoodRemedy
Heatsink cloggedIn-out temp rise below 8CZero (blow out)HighCompressed air cleaning
Fan worn outSlow speed or noiseLowHighReplace with same model
High ambientCabinet above 40CMediumMediumCooling or derate
Bus capacitors agedCapacitance below 80%MediumMedium, past 8 yearsMatched set replacement
Parameters alteredCompare with backupZeroMediumRestore backup
Current sensing driftClamp meter gap above 5%MediumLowCalibrate or swap board
IGBT degradedModule runs hotHighLowModule or unit change

5. Notes

Preventive maintenance every two years for drives past seven: blow out, re-fan, measure capacitance, re-torque terminals, IR survey; log it per unit, and never reset an overload trip twice without stopping to investigate.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance per GB/T 12668.501 / IEC 61800-5-1; equipment safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Resetting an overload trip and restarting: with aged capacitors the ripple is already large and the third restart punctures the rectifier at five times the repair cost
② Mixing old and new capacitors: the new ones carry the extra ripple and swell within three months, so the swap was wasted
③ Skipping switchroom cooling at 40 degrees ambient: one percent of rating per degree leaves the drive at seventy percent in summer and a fortnight is spent chasing the load instead

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.