Most modern VFDs ship with a PID autotune routine that can cut commissioning time in half, yet many technicians run it once and never look back. This page explains how autotune works, the preconditions to check, how to verify the result, and when manual trimming is unavoidable.
Autotune works by injecting a small step or pulse disturbance and measuring the loop response: dead time, rise time and overshoot. From these it estimates Kp, Ti and Td with a Ziegler-Nichols style algorithm. Before triggering it, three preconditions matter. The feedback signal must be steady, with 4~20mA ripple below 0.5 percent of span. The actuator must move freely, no stuck valve, no cavitating pump. And the process must tolerate a small excursion, say plus or minus 0.02MPa on a constant-pressure water line. During tuning the drive deliberately swings its output 2 to 5 percent around the setpoint, so neighbouring interlocks should be told in advance.
Verify the result in three steps. Apply a 10 percent setpoint step: overshoot should stay under 5 percent and oscillation should settle within one and a half cycles. In steady state, output frequency wobble should be within plus or minus 1Hz and the controlled variable within a quarter of the tolerance band. Kick in a disturbance, say opening a branch valve, and recovery should take under 30 seconds. Autotune usually returns conservative gain, so raising Kp by 30 to 50 percent is a fair first trim; high-frequency chatter means the derivative term is amplifying noise, so add 0.5 to 1s of derivative filtering or switch the D term off.
Autotune fails on long-dead-time processes such as pH neutralisation, on strongly nonlinear loads where pump gain differs by a factor of two across the speed range, on worn feedback devices with dead zones, and on multi-pump systems where a set tuned for one pump destabilises with two. The manual fallback starting point is Kp 0.5, Ti 30s, derivative off, changing one parameter at a time.
| Load type | Kp | Ti | Td | Sample period |
|---|---|---|---|---|
| Centrifugal pump, constant pressure | 1.5~3 | 10~30s | Off | 0.1~0.5s |
| Fan, temperature duty | 0.5~1.5 | 60~300s | Off or filtered | 2~10s |
| Air compressor, pressure | 2~5 | 5~20s | Off | 0.1s |
| Level, large volume | 0.3~1 | 60~600s | Off | 1~5s |
| Temperature, furnace | 1~2 | 100~500s | 10~60s | 1~5s |
| Flow control | 0.5~1.5 | 2~10s | Off | 0.05~0.2s |
Retune after any seasonal change, load swap or network modification, and file the before-and-after parameters with the step response plot in the commissioning report so future troubleshooting has a baseline.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per IEC 60204-1 / GB/T 5226.1; water supply practice per GB 50015. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.