Diagnosing noise and vibration during VFD commissioning

A motor that suddenly whines or shakes after a drive retrofit is rarely a bad motor; carrier frequency, mechanical resonance or a mis-set parameter is the usual culprit. This page sorts the noise by ear and spectrum, then works through carriers, parameters and resonance with a diagnostic order table.

1. How it works

The first split is a coast-down test: noise or vibration that persists during free coasting is mechanical, bearings or alignment or balance, while what vanishes the instant power is cut is electromagnetic. Subdivide the electromagnetic band: carrier noise sits at 2~16kHz with a fixed pitch, while slip harmonics sit from a few hundred Hz to a few kHz and move with speed. A phone spectrum app gives a first fix: a peak that stays put while speed changes is carrier or a structural natural frequency; a peak that tracks speed linearly is mechanical, unbalance at one times running speed and misalignment at two. Low-frequency shudder at a few Hz is typical V/F torque ripple at low speed, helped by boost or a switch to vector control.

2. Numbers and practice

Carrier whine is the commonest complaint: raising the carrier from the 4kHz default to 8~12kHz softens it at once, at the price of roughly 0.5 percent efficiency per step and higher leakage current that trips RCDs more easily; above 55kW stay at or below 8kHz. Parameter noise includes over-boosted V/F curves, where the motor saturates at low speed with a dull hum and extra heat, cured by dropping torque boost from the 15 percent default to 5~10 percent; beat notes between carrier and output frequency show as periodically shifting tone, cured by stepping the carrier to another band; and a freshly commissioned vector mode that whines usually has speed-loop gain too high, so back it off 20 to 30 percent.

3. Pitfalls and fixes

Resonance appears when the widened speed range sweeps a structural natural frequency: vibration spikes in one narrow speed band and is normal elsewhere. Pick one of three cures, a skip-frequency band such as 35~38Hz where the drive will not dwell, stiffening the base to raise the natural frequency, or damping pads; a drive offers at most three skip bands, and if that is not enough the structure must change. Installation faults show their own signatures, misalignment at two times speed with axial emphasis, loose foundation bolts growing with load, belt tension faults as beat notes. Survey by slow frequency sweep and re-run it after any foundation or piping change.

4. Noise and vibration diagnostic order

SymptomFirst checkLikely causeRemedyVerification
Fixed high whineSpectral peak does not track speedCarrier too lowRaise carrier to 8~12kHzListening plus drive temperature
Dull low humLow-speed band, motor hotTorque boost too highDrop to 5~10 percentCurrent comparison
Shaking in one speed bandOnly around one speedMechanical resonanceSkip band or stiffeningRepeat frequency sweep
Vibration on coastPersists without powerAlignment or bearingsLaser alignment, new bearingsTwice-speed amplitude
Whine in vector modeAppears after mode switchSpeed gain too highReduce gain 20~30 percentStep response
Periodic shudderTone cycles slowlyBeat or belt faultChange carrier band, check tensionLocate by ear

5. Notes

Split by coast test, locate by spectrum, then treat the cause; log the original carrier before changing it, watch temperatures for half an hour afterwards, and record every skip band in the parameter sheet so operators do not mistake it for a fault.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Vibration limits per GB/T 6075 / ISO 10816; equipment safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Masking resonance with a higher carrier: the whine goes but the resonance speed remains and the bearings keep paying, with vibration data over limit within six months
② Commissioning on default torque boost: low-frequency saturation pushes motor temperature rise past limits and ages the insulation twice as fast
③ Skip bands set but never recorded: the parameters vanish with the next drive swap and the resonance returns for a second round of diagnosis

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.