Hoisting needs 150 percent torque at start while plain V/F runs out of breath below 5Hz. Torque boost exists to fix exactly that band. This page covers how much boost to set, the cost of overdoing it, and how to diagnose boost that refuses to work.
In fixed-ratio V/F the stator resistance drop grows from about 3 percent of voltage at rated frequency to over 15 percent at low frequency, starving the flux: without compensation, available torque at 5Hz can fall to 40~60 percent of rating. Boost lifts the low-frequency end of the voltage curve, giving 15~25 percent at 5Hz instead of the proportional 10 percent, restoring torque for cranes, extruders and presses.
Practical settings: 2~3 percent for light loads, 5 percent for conveyors, 8~10 percent for heavy starts such as hoists, judged by three checks: starting current within 1.2 times rated, no deep magnetic hum, and unloaded 5Hz current below half of rated. Automatic boost, which scales with measured load current, is the better choice for cranes. Overboost saturates the core, distorts the magnetizing current and heats the motor within minutes of low-speed running, so watch the ammeter, not the ears.
| Load type | Suggested boost | Unloaded 5Hz current | Caution |
|---|---|---|---|
| Fans and pumps | 1~2 percent | Below 30 percent rated | More just heats |
| Conveyors and mixers | 4~5 percent | About 40 percent rated | Trim by starting current |
| Extruders and calenders | 8~10 percent | Below 50 percent rated | Beyond 10 percent use vector |
| Hoisting mechanisms | 8~12 percent or auto | Below 50 percent rated | Coordinate with brake timing |
| Machine spindles | 2~3 percent | About 35 percent rated | Field-weakening handled separately |
The iron rule is to watch the ammeter: raise boost one step at a time at unloaded 5Hz and back off as soon as the current turns upward. Recheck hoisting boost quarterly, since brake and rope wear shift the starting torque demand.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety for machinery follows IEC 60204-1 / GB/T 5226.1; motor fundamentals follow IEC 60034-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.