A drive two frames too large wastes money and plants a harmonics problem, one frame too small trips daily and cooks its modules. This page lays out the real consequences of both and a current-based sizing check that lands within half a frame.
Oversizing costs in three ways: purchase price roughly doubles two frames up; the larger rectifier draws bigger absolute harmonic currents and worsens input power factor at light load, raising treatment costs for the cabinet and the supply; and the electronic thermal model is calibrated to the drive rating, so with a motor at 60 percent of drive rating a 130 percent motor overload may never trip the drive, leaving the winding unprotected. The margin can be had anyway by setting the current limit instead.
Undersizing shows up as: automatic derating and summer overtemperature trips, starting failures when the small frame hits its current limit, and module life halved by junction temperatures at 90 percent loading, plus the case where motor magnetizing current alone exceeds the drive rating and it never starts at all. The correct check is four steps: read the motor nameplate current, apply the duty factor of 1.1~1.15 for constant torque or 1.2~1.3 for frequent heavy starts, pick the frame by current with G and P versions distinguished, and verify the unloaded motor current stays under 40~50 percent of drive rating.
| Deviation | Direct result | Hidden risk | Correction |
|---|---|---|---|
| One frame too large | 30~80 percent more cost | Bigger harmonics, poorer PF | Use the margin via current limit |
| Two frames or more | Doubled price, cabinet space | Thermal model misses motor | Reset protection by motor current |
| 5~10 percent small | Summer derating trips | Short module life | Improve cabinet cooling |
| 20 percent small | Stall trips on heavy start | Modules overloaded | Move up one frame |
| Severely small | Overcurrent at magnetizing | Cannot commission | Reselect by measured current |
Never size from a power cross-table alone: pole count shifts current by 10~20 percent and duty shifts it further. Size by current, set margin by duty, correct by measurement.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive ratings and sizing per IEC 61800-2 / GB/T 12668.501, machine safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.