Every brand has its own code list, but the alarm families are the same ten everywhere. Current, voltage, overload, heat, phase loss and comms - with causes and field actions per class.
Alarm families transcend brands: overcurrent OC, instantaneous output current beyond the limit; overvoltage OU, bus above threshold; undervoltage LU, bus sagging; overload OL, current above rating for too long; overheating OH, heatsink or motor; phase loss PF; communication CE. Read every alarm with three elements: the code, the operating condition - starting, running, decelerating, stopped - and whether it resets. The same code means different things in different conditions, and that is the core of fast diagnosis.
The frequent ones: overcurrent at start means an output short, cable insulation or acceleration far too short - defaults near 5s want 10~30s on high-inertia loads; during running, look at load shocks and vector mode matching. Overvoltage on decel calls for longer decel times or a braking resistor; at idle, check the supply tap. Overload: set the electronic thermal current to the motor nameplate value, not the drive rating - the classic beginner error - then check for stalling and unbalanced phases. Overheat: fan turning, fins clear, ambient below 40C, mounting clearance 10cm at the sides and 15cm above. Undervoltage points to supply sags, aged bus capacitors or a weak upstream contact. And the rule of three: an alarm that comes back after three resets gets investigation, not another reset.
| Alarm family | Typical codes | Usual causes | Field action |
|---|---|---|---|
| Overcurrent OC | F30001, E.OC1 and kin | Short accel, output short | Longer accel, check insulation |
| Overvoltage OU | F30002, E.OV1 | Regen on decel, high input | Longer decel, braking unit |
| Overload OL | F30005, E.THT | Thermal set to drive rating | Set to motor current, check load |
| Overheat OH | F30004, E.FIN | Fan, blocked fins, hot room | Clean, cool, check clearance |
| Undervoltage LU | F30003, E.UVT | Supply sag, aged capacitors | Check supply, test bus caps |
| Communication CE | F3-family code, E.MOD | Wiring, address, noise | Check line, address, earthing |
Log the code, note the condition, change one parameter, reset no more than three times. Read the manual appendix before opening the cabinet - understand the families and any brand becomes familiar within minutes.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable speed drives and their tests per GB/T 12668.2 (IEC 61800-2), machinery protection per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.