Bias and gain calibration for VFD analogue inputs

A potentiometer sweeping to 10V while the drive only reads 48Hz, or 4mA refusing to mean zero speed: nine times out of ten the bias and gain are uncalibrated. This page explains the mapping, a four-step calibration and the classic wiring mistakes.

1. How it works

Analogue setpoints map a signal range onto a frequency range: 0~10V to 0~50Hz, or 4~20mA to 0~50Hz or reversed. Bias sets the frequency at minimum signal and gain at maximum. Factory defaults assume 0~10V, so a 1~5V sensor or a live-zero 4~20mA loop forces a recalibration. Symptoms of error are familiar: full-scale input lands short of 50Hz when gain is low, and the motor creeps at rest when bias sits high.

2. Practice and pitfalls

Calibrate in four steps: apply the minimum signal and trim bias until the drive shows the target, apply maximum and trim gain, apply mid-scale and confirm the reading within 1 percent of half-range, then save and verify under load. The signal type must be set to 4~20mA explicitly, otherwise the drive treats 4mA as 20 percent and zero never lines up. The live-zero also buys wire-break detection below 2mA, which voltage signals cannot offer, so use twisted screened pairs grounded at one end, keep them out of power trays, and check input impedances of roughly 250 ohms for current and 10k for voltage loops.

3. Analogue mapping quick reference

Signal typeMinimum maps toMaximum maps toBreak detectable
0~10V0V = 0Hz10V = 50HzNo
2~10V2V = 0Hz10V = 50HzBarely
1~5V1V = 0Hz5V = 50HzNo
0~20mA0mA = 0Hz20mA = 50HzNo
4~20mA4mA = 0Hz20mA = 50HzBelow 2mA yes

4. Notes

The chant: pick the type, zero first, full scale second, verify mid-scale, write the mapping on the panel. When the loop misbehaves, measure the source with a meter before blaming the drive; a 2 percent mismatch points at calibration or wiring.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Analogue signal standards per IEC 60381-2 / GB/T 3369.2, electrical safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Configuring a 4~20mA loop as 0~20mA: 4mA becomes 20 percent setpoint and the motor creeps at rest forever
② Twiddling bias and gain by feel: full scale tops out at 48Hz and a 4 percent speed mismatch desynchronises the whole line
③ Grounding the screen at both ends: ground loops inject into the setpoint and the speed dances whenever a nearby machine starts

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.