Relays look simple yet burn contacts every day. This page covers derating by load type, arc suppression for inductive loads, and how to read life curves.
The nameplate AC250V/5A applies to resistive loads only. Derate by load: incandescent lamps inrush 10 times and take one third of rating; motors start at 5 to 7 times and take 0.2 to 0.3; transformers surge 15 to 30 times and take 0.1; switching supplies take about 0.2. DC is far harder on contacts because the arc never crosses a zero crossing: the same contact handles only one fifth to one tenth of its AC capacity, so AC250V/5A means under 1 A at DC24V and 0.2 A class at DC110V. Keep 20 percent headroom on top of derating.
Interrupting inductive loads generates back-EMF of 10 to 20 times supply, and opening a 24 V AC coil can spike contact voltage past 300 V, drawing an arc that erodes metal. Fit a freewheeling diode across DC loads, cathode to positive, or an RC snubber, 0.1 to 0.47 microfarads with 47 to 100 ohms, for AC. Life arithmetic: resistive duty starts at 100000 operations; unsuppressed inductive duty can weld contacts within 10000, while suppression restores 80000 plus.
Failure modes: welded contacts from unsuppressed inductance, contact resistance a few milliohms and refusing to open; eroded contacts showing over 100 mV drop under load; burnt coils from overvoltage or excessive cycling; and stuck armatures in leaky sealed relays. Never use power relays for milliamp signal switching; their contacts oxidise without the self-cleaning of real load current. Use dry-reed or solid-state devices for signals.
| Load type | Inrush multiple | Derating factor | Typical use |
|---|---|---|---|
| Resistive | 1 times | 1.0 | Heaters, indicators |
| Incandescent | 10 to 15 times | 0.3 | Lighting control |
| Motor | 5 to 7 times | 0.2 to 0.3 | Contactor drive |
| Transformer | 15 to 30 times | 0.1 | Primary switching |
| Switch-mode supply | 10 to 20 times | 0.2 | DC distribution |
| DC inductive | Voltage 10 to 20 times | 0.1 to 0.2 | Solenoids, clutches |
Label every relay with its load type so replacements match, and never put a 5 A relay where 10 A lived. Before fleet use, life-test three samples for 1000 loaded operations and archive the data.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Relay contact performance follows the IEC 61810 series and GB/T 21711.7; coordination with machinery follows GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.