Siemens G120: switching between V/F and vector control via P1300

On the G120, one parameter decides the control mode: P1300. This page gives the switching path, the companion settings such as motor identification, and the verification steps after the change so low-speed torque behaves as advertised.

1. How it works

Set P1300 to 0 for linear V/F, 2 for square-law V/F on fans and pumps, 3 for flux-enhanced V/F, or 20 and 21 for sensorless vector in frequency or torque mode. The drive requires a quick-commissioning cycle (P0010=1, then P3900=3 to save and exit) before the new mode takes effect. After switching to mode 20 or 21, motor identification via P1900 must be repeated, otherwise the motor model is wrong and low-speed torque falls short.

2. Practice and pitfalls

Choose mode 2 for fans and pumps, mode 0 or 3 for constant-torque conveyors and mixers, and mode 20 where low-speed stiffness and speed accuracy within about 0.5 percent matter, such as winding or hoisting. After the change, jog at P1058 around 5Hz unloaded and check the current stays below 40 percent of rated, then test 5Hz and 50Hz under load before handing the line to production.

3. Control mode selection table for the G120

P1300ModeTypical loadLow-speed behaviorMotor ID needed
0Linear V/FGeneral constant torqueFair, needs boostNo
2Square V/FFans and pumpsWeak below 10HzNo
3Flux V/FDemanding constant torqueGoodRecommended
20Sensorless vector, frequencyWinding and hoisting150 percent torque at 1HzMandatory
21Sensorless vector, torqueTension controlGoodMandatory

4. Notes

Three steps after every mode change: repeat motor identification, jog unloaded and verify current, then record current and speed at 5Hz and 50Hz under load before releasing to production.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Commissioning follows the Siemens operating instructions with machine electrical safety per IEC 60204-1 and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Changing P1300 without motor identification: the vector model misreads flux, real torque falls short and overcurrent trips follow
② Rotating identification with the coupling still loaded: the routine fails with a fault or captures wrong parameters and plants a latent problem
③ First full-load run straight after switching to vector mode: unchecked torque limits stall the shaft mid-cycle and jam the workpiece

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.