On the G120, one parameter decides the control mode: P1300. This page gives the switching path, the companion settings such as motor identification, and the verification steps after the change so low-speed torque behaves as advertised.
Set P1300 to 0 for linear V/F, 2 for square-law V/F on fans and pumps, 3 for flux-enhanced V/F, or 20 and 21 for sensorless vector in frequency or torque mode. The drive requires a quick-commissioning cycle (P0010=1, then P3900=3 to save and exit) before the new mode takes effect. After switching to mode 20 or 21, motor identification via P1900 must be repeated, otherwise the motor model is wrong and low-speed torque falls short.
Choose mode 2 for fans and pumps, mode 0 or 3 for constant-torque conveyors and mixers, and mode 20 where low-speed stiffness and speed accuracy within about 0.5 percent matter, such as winding or hoisting. After the change, jog at P1058 around 5Hz unloaded and check the current stays below 40 percent of rated, then test 5Hz and 50Hz under load before handing the line to production.
| P1300 | Mode | Typical load | Low-speed behavior | Motor ID needed |
|---|---|---|---|---|
| 0 | Linear V/F | General constant torque | Fair, needs boost | No |
| 2 | Square V/F | Fans and pumps | Weak below 10Hz | No |
| 3 | Flux V/F | Demanding constant torque | Good | Recommended |
| 20 | Sensorless vector, frequency | Winding and hoisting | 150 percent torque at 1Hz | Mandatory |
| 21 | Sensorless vector, torque | Tension control | Good | Mandatory |
Three steps after every mode change: repeat motor identification, jog unloaded and verify current, then record current and speed at 5Hz and 50Hz under load before releasing to production.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Commissioning follows the Siemens operating instructions with machine electrical safety per IEC 60204-1 and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.