An induction motor fixes its shaft speed by supply frequency, pole pair count and slip. This page walks through the formula n=60f(1-s)/p with worked examples, so you can predict shaft speed before touching any drive parameter on site.
The formula n=60f(1-s)/p governs everything: a 4-pole motor has p=2, so at 50Hz the synchronous speed is 1500r/min and full-load speed sits at 1420~1470r/min with 2~5 percent slip. Lower the output frequency to 25Hz and the shaft drops to roughly 720r/min. Always remember p means pole pairs, not pole count, or every calculation lands a factor of two off.
Below rated frequency the drive keeps flux constant and delivers constant torque; above 50Hz the voltage cannot rise past the 380V supply, flux weakens and available torque falls about 15~20 percent for every extra 10Hz. At low frequency without boost compensation, stator resistance eats the voltage margin and torque can fall to half of rating near 5Hz, which is exactly why V/F boost curves exist.
| Poles | Pole pairs p | Sync speed | Full-load speed | Speed at 25Hz |
|---|---|---|---|---|
| 2 poles | 1 | 3000r/min | 2850~2940r/min | about 750r/min |
| 4 poles | 2 | 1500r/min | 1420~1470r/min | about 360r/min |
| 6 poles | 3 | 1000r/min | 940~980r/min | about 250r/min |
| 8 poles | 4 | 750r/min | 700~730r/min | about 185r/min |
| 10 poles | 5 | 600r/min | 560~590r/min | about 150r/min |
| 12 poles | 6 | 500r/min | 460~490r/min | about 125r/min |
Use this table to sanity-check any drive commissioning job: read the motor nameplate, find the expected full-load speed, then compare against the drive output frequency reading before blaming the equipment.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 755 for rotating machine ratings and IEC 60034-1 for performance definitions of induction motors. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.