The accuracy of drive torque compensation is rooted in the motor nameplate entered at commissioning. This page shows how rated voltage, current, frequency and speed each steer the compensation, and how to verify the result.
The compensation algorithm consumes the four nameplate values typed in during quick commissioning: rated voltage, current, frequency and speed. Any wrong entry skews the equivalent circuit and the compensation voltage with it. Classic mistakes include typing the bus voltage level instead of 380V, entering a synchronous speed of 1500 instead of the nameplate 1440 which silently disables slip compensation, and copying the drive rating instead of the motor current. An error above 10 percent shows up as either weak low speed or overexcited heating.
Enter 380V as 380, take the 50Hz line when the plate lists both, and use the nameplate 1440r/min so slip compensation works. After entry, run a rotating motor identification so the drive measures stator resistance itself. Verify in three steps: unloaded 5Hz current within 30~50 percent of rated, linear speed tracking from 50Hz down to 5Hz without jumps, and cold-versus-hot 5Hz drift below 1 percent. Re-enter everything whenever the motor changes, including after a winding rewind.
| Parameter | Correct source | Typical mistake | Compensation result |
|---|---|---|---|
| Rated voltage | 380V from plate | 400V or bus level typed | Low-frequency overvoltage and heat |
| Rated current | 50Hz line on plate | Drive rating copied | Limits and compensation skewed |
| Rated frequency | 50Hz on plate | 60Hz motor entered as 50 | Flux overshoot and whine |
| Rated speed | Plate value like 1440 | Synchronous 1500 typed | Slip compensation dead |
| Power factor and efficiency | Plate or defaults | Guessed above 0.9 | Model accuracy drops |
The fixed commissioning ritual: enter four nameplate numbers, run rotating identification, then verify unloaded 5Hz current. Repeat the ritual for any motor swap, rewind or drive board replacement.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Nameplate ratings per IEC 60034-1 / GB/T 755, commissioning safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.