Torque compensation depends on the nameplate: get four numbers right or the correction skews

The accuracy of drive torque compensation is rooted in the motor nameplate entered at commissioning. This page shows how rated voltage, current, frequency and speed each steer the compensation, and how to verify the result.

1. How it works

The compensation algorithm consumes the four nameplate values typed in during quick commissioning: rated voltage, current, frequency and speed. Any wrong entry skews the equivalent circuit and the compensation voltage with it. Classic mistakes include typing the bus voltage level instead of 380V, entering a synchronous speed of 1500 instead of the nameplate 1440 which silently disables slip compensation, and copying the drive rating instead of the motor current. An error above 10 percent shows up as either weak low speed or overexcited heating.

2. Practice and pitfalls

Enter 380V as 380, take the 50Hz line when the plate lists both, and use the nameplate 1440r/min so slip compensation works. After entry, run a rotating motor identification so the drive measures stator resistance itself. Verify in three steps: unloaded 5Hz current within 30~50 percent of rated, linear speed tracking from 50Hz down to 5Hz without jumps, and cold-versus-hot 5Hz drift below 1 percent. Re-enter everything whenever the motor changes, including after a winding rewind.

3. Nameplate entry quick reference

ParameterCorrect sourceTypical mistakeCompensation result
Rated voltage380V from plate400V or bus level typedLow-frequency overvoltage and heat
Rated current50Hz line on plateDrive rating copiedLimits and compensation skewed
Rated frequency50Hz on plate60Hz motor entered as 50Flux overshoot and whine
Rated speedPlate value like 1440Synchronous 1500 typedSlip compensation dead
Power factor and efficiencyPlate or defaultsGuessed above 0.9Model accuracy drops

4. Notes

The fixed commissioning ritual: enter four nameplate numbers, run rotating identification, then verify unloaded 5Hz current. Repeat the ritual for any motor swap, rewind or drive board replacement.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Nameplate ratings per IEC 60034-1 / GB/T 755, commissioning safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Typing the drive current instead of the motor current: real current sits at 70 percent of the limit and overload protection never fires until the winding burns
② Entering a 60Hz import motor as 50Hz: flux overshoots by 20 percent, the core saturates and the winding dies within months
③ Skipping re-identification after a motor swap: 20 percent resistance mismatch skews low-speed compensation past 15 percent and the vibration hunt begins

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL