Contactor sizing by motor power and utilisation category

What size contactor for a 7.5 kW motor? Power alone is not enough; the utilisation category comes first. This page covers AC-1 to AC-4, the current-based sizing method, and where derating applies.

1. How it works

Start from the category, not the kilowatts. AC-1 covers resistive loads at full rated current; AC-3 is the standard cage-motor start-and-run duty sized on full-load current; AC-4 covers plugging, inching and frequent reversing where contacts see 6 to 8 times rated repeatedly, and the same frame carries roughly half its AC-3 rating in AC-4 duty. Mixed duty beyond 10 percent AC-4 must be sized as AC-4.

2. Numbers and practice

Full-load current follows I = P/(√3·U·η·cosφ), about 2 A per kW on 380 V. For 7.5 kW at 0.87 efficiency and 0.84 power factor, I ≈ 15.5 A: pick an 18 A class contactor such as a CJX2-1810 in AC-3 duty with 10 to 15 percent margin, or step up to 32 A if inching is frequent. Intermittent duty is converted by load factor, and operating rates above the hourly limit of 600 to 1200 operations force a larger frame.

3. Pitfalls and fixes

Derate for ambient above 40 C by 5 to 10 percent per 10 K, for cramped cabinets by 10 to 20 percent, and for altitude beyond 2000 m by 0.5 percent per 100 m. Upsize for capacitors (AC-6b, inrush tens of times rated, needs special contactors or suppression), discharge lighting (AC-5a) and transformer switching (AC-6a). Check coil voltage tolerance of 85 to 110 percent against the control supply, and match PLC output capacity to the coil inrush when the PLC drives small contactors directly.

4. Utilisation categories and sizing rules

CategoryTypical loadCurrent shockSizing rule
AC-1Heaters, resistorsWithin 1xFull rated current
AC-2Slip-ring motorsAbout 2.5xClose to AC-3
AC-3Cage motor DOL6~8x brieflyFLC plus 15%
AC-4Inching, plugging6~8x repeatedHalf the AC-3 rating
AC-5a/5bDischarge/incandescent lampsSurges several timesSize by surge
AC-6a/6bTransformers/capacitorsInrush tens of timesSpecial types or suppression

5. Notes

Workflow: fix the category, compute the full-load current, pick the frame from the catalogue value for that category, verify coil voltage and auxiliary count and mounting, then upsize one step for cabinet heat. Never cross-read the AC-3 and AC-4 columns of the datasheet.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.4 for contactor ratings and categories and IEC 60204-1 for protection coordination. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Using AC-3 data for frequent inching: AC-4 wear rates kill the contacts within months
② Skipping cabinet-temperature derating: at 55 C inside the enclosure in summer the contacts weld under load
③ Switching capacitors with an ordinary AC-3 contactor: inrush welds the contacts permanently closed and cascades trips

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.