What size contactor for a 7.5 kW motor? Power alone is not enough; the utilisation category comes first. This page covers AC-1 to AC-4, the current-based sizing method, and where derating applies.
Start from the category, not the kilowatts. AC-1 covers resistive loads at full rated current; AC-3 is the standard cage-motor start-and-run duty sized on full-load current; AC-4 covers plugging, inching and frequent reversing where contacts see 6 to 8 times rated repeatedly, and the same frame carries roughly half its AC-3 rating in AC-4 duty. Mixed duty beyond 10 percent AC-4 must be sized as AC-4.
Full-load current follows I = P/(√3·U·η·cosφ), about 2 A per kW on 380 V. For 7.5 kW at 0.87 efficiency and 0.84 power factor, I ≈ 15.5 A: pick an 18 A class contactor such as a CJX2-1810 in AC-3 duty with 10 to 15 percent margin, or step up to 32 A if inching is frequent. Intermittent duty is converted by load factor, and operating rates above the hourly limit of 600 to 1200 operations force a larger frame.
Derate for ambient above 40 C by 5 to 10 percent per 10 K, for cramped cabinets by 10 to 20 percent, and for altitude beyond 2000 m by 0.5 percent per 100 m. Upsize for capacitors (AC-6b, inrush tens of times rated, needs special contactors or suppression), discharge lighting (AC-5a) and transformer switching (AC-6a). Check coil voltage tolerance of 85 to 110 percent against the control supply, and match PLC output capacity to the coil inrush when the PLC drives small contactors directly.
| Category | Typical load | Current shock | Sizing rule |
|---|---|---|---|
| AC-1 | Heaters, resistors | Within 1x | Full rated current |
| AC-2 | Slip-ring motors | About 2.5x | Close to AC-3 |
| AC-3 | Cage motor DOL | 6~8x briefly | FLC plus 15% |
| AC-4 | Inching, plugging | 6~8x repeated | Half the AC-3 rating |
| AC-5a/5b | Discharge/incandescent lamps | Surges several times | Size by surge |
| AC-6a/6b | Transformers/capacitors | Inrush tens of times | Special types or suppression |
Workflow: fix the category, compute the full-load current, pick the frame from the catalogue value for that category, verify coil voltage and auxiliary count and mounting, then upsize one step for cabinet heat. Never cross-read the AC-3 and AC-4 columns of the datasheet.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.4 for contactor ratings and categories and IEC 60204-1 for protection coordination. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.