The alarm history is the cheapest diagnostic you own, yet most people clear it after glancing at the code. This page covers extracting records, combining them into a timeline, and building an alarm log that finds root causes.
Modern drives log far more than a code: alarm number, timestamp, command and feedback position, speed, torque, bus voltage, regeneration load, and on better units parameter snapshots around the event. A6-class drives keep the last 10 to 30 events, exportable via the panel or PC software. Export before clearing; once gone it is gone forever. The torque and speed traces at the trip moment do half the diagnosis: torque pegged at its limit suggests a mechanical stall, speed overshoot suggests tuning.
Single events mislead, so build a timeline: sort every axis alarm in the window, add PLC alarms and operator notes. Patterns to hunt: an A-axis overload two seconds before a B-axis overtravel usually means a mechanical jam came first; the same alarm at the same time daily points to grid dips or HVAC start-up; alarms after shift change point to handling differences. Read bus voltage together with regeneration load to separate aggressive deceleration from an ageing braking resistor.
Start the log with three columns: date and time, code and axis, action and result. Review monthly; any code exceeding three occurrences deserves a root-cause project, not another reset. Record the machine state around intermittent trips: motion being executed, ambient temperature, material batch. These details are the keys to reproduction, and the log travels with the machine between shifts.
| Field | What it shows | Analysis focus |
|---|---|---|
| Alarm code | Fault category | Hard or soft per manual |
| Timestamp | Correlation with duty | Fixed hour: grid or HVAC |
| Command versus feedback | Lost counts or overtravel | Large gap: mechanics |
| Torque trace | Limit saturation | Saturated: stall or step load |
| Bus voltage | Regeneration state | High: brake resistor ageing |
| Parameter snapshot | Tampering evidence | Diff against baseline |
Never clear an alarm without exporting the history first; make it a crew rule. Quarterly, run a focus review of the most frequent codes; most recurring faults die at that step.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Diagnostics and indication follow GB/T 5226.1; drive communication and data access reference IEC 61800 and IEC 61158 profiles. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.