The MD500 carries a full PID loop for constant pressure or temperature duty without an external PLC, but the parameter groups and the reference-feedback wiring must be understood first. This page maps the group, the hookup and the tuning order.
The PID parameters live mainly in group A and the function groups: reference source (numeric, AI1/AI2 or fieldbus), feedback source, reference and feedback scaling, proportional gain 0.1~10, integral time 0.5~60s, differential time typically unused, sample period 0.01~1s, and the output clamp that caps the frequency. Walk the group in the manual and build a cross-reference table before touching anything.
For constant pressure: a 4~20mA transmitter on AI2 with the feedback range mapped to 0~1MPa at 20mA, and a 0.3MPa target set numerically as 60 percent or trimmed from AI1. Check the action polarity, since pump speed raising pressure means the loop must act negatively on the feedback; reversed polarity runs away, so first test at a small output clamp unloaded. Tune P then I: Kp from 0.5, typically 1~3 for pumps, Ti from 20s, typically 10~30s, no D for water. Verify a 10 percent step with under 5 percent overshoot settling inside 30 seconds, no night oscillation, and pump-changeover dips recovering within 0.02MPa.
| Parameter | Typical range | Start value | Symptoms of error |
|---|---|---|---|
| Proportional Kp | 0.1~10 | 1~3 for pumping | High oscillates, low lags |
| Integral Ti | 0.5~60s | 10~30s | Small leaves offset, large oscillates |
| Differential Td | 0~1s | 0 for water | Noise sensitive |
| Sample period | 0.01~1s | 0.1s | Long lags, short jitters |
| Output clamp | 20~100 percent | By process ceiling | Response versus safety |
| Feedback break | Alarm or stop | Stop | By process risk |
Confirm three prerequisites before closing the loop: feedback type and range matched, action polarity correct, output clamp aligned with process limits. Change one parameter at a time and archive the step responses.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive functions per IEC 61800-2 / GB/T 12668.501, pumping electrical safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.