Starting a loaded belt is the classic conveyor problem: huge starting current and violent tension shock. VFD soft starting is the mainstream answer, and this page covers the sizing rules and parameter settings in one pass.
A belt is constant torque with very large inertia: full-load starting torque reaches 130~150 percent of running, and starts last tens of seconds. Size a heavy-duty G frame at 1.15~1.3 times motor current, the top of the range for frequent starts or inclined conveying. Long belts with head and tail drives need balanced power: identical drives with master-follower load sharing, keeping the current mismatch within 5 percent or the tension skews and the belt wanders.
Use an S-curve start: a gentle 3~5 second tension-building segment up to 10 percent frequency, then a normal ramp, then a soft arrival at speed, the whole start 30~90 seconds by belt length. Enable 5~8 percent torque boost for loaded starts or use vector mode for low-speed torque, clamp the acceleration so roller-belt slip stays under 2~4 percent, and stop with a ramp plus DC injection. Inclined belts always keep a mechanical backstop alongside drive braking. Store separate loaded and unloaded parameter sets and switch them by terminal, and add output reactors for long motor cables.
| Point | Recommended practice | Common mistake | Consequence |
|---|---|---|---|
| Capacity factor | 1.15~1.3 times current, G frame | P frame or 1.0 times | Stall trips on start |
| Start curve | S-curve over 30~90s | Fast linear ramp | Tension shock tears the splice |
| Torque boost | 5~8 percent loaded | None | Slip at loaded start |
| Multi-drive balance | Current mismatch under 5 percent | Independent tuning | Power skew and belt wander |
| Reverse prevention | Drive braking plus backstop | Drive alone | Runback of loaded belt, a real hazard |
Acceptance looks at four things: a one-shot loaded start, no visible belt surge during it, current balance within 5 percent, and reliable e-stop interlocks. Function-test the reverse prevention quarterly on inclined lines; that is a safety item, not an energy one.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Belt conveyor safety per GB 14784; electrical safety per IEC 60204-1 / GB/T 5226.1 and drives per IEC 61800-2. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.