Level loops differ fundamentally from pressure loops: huge volumes, long lags and a tolerated band of fluctuation, so the tuning logic changes. This page covers the wiring, the parameter traits and the anti-oscillation measures for supply and drainage duty.
Level is a large-capacity slow process: a 100-cubic-metre tank with a 10 cubic-metre-per-hour imbalance takes tens of minutes to show, and the double lag makes aggressive PID oscillate. Most processes tolerate a band, say 2~3.5m, and band control beats fixed setpoint on energy: stop the inlet pump at the upper limit, restart at the lower, and starts per day actually drop. Fixed setpoint is for processes that cannot float at all, such as drum levels, which follow their own rules.
Wiring: a 4~20mA level transmitter into the drive AI, the target set numerically, or band control through relay outputs. Parameters: small Kp of 0.3~1, long integral of 60~600s, sample period 1~5s, no derivative. Mind the action sign, since inlet pumps slow down as level rises while drainage pumps speed up. Set the frequency floor at 20~25Hz because pumps lose efficiency and cavitate below it. Anti-oscillation: a deadband of 0.1~0.2m, integral separation on large errors, and hard-wired float switches for overflow and dry-run protection that bypass the analogue loop entirely.
| Parameter | Pressure duty | Level duty | Reason |
|---|---|---|---|
| Proportional Kp | 1~3 | 0.3~1 | Large volume needs small gain |
| Integral Ti | 10~30s | 60~600s | Long lag wants slow integral |
| Sample period | 0.1s | 1~5s | Slow process, slow sampling |
| Control mode | Fixed setpoint | Band preferred | Use the buffer to save energy |
| Derivative | Usually off | Off | Amplifies noise for nothing |
| Deadband | 0.01MPa | 0.1~0.2m | Stops hunting around target |
Ask first what the process needs: fixed level or a tolerated band. After tuning, step the inflow by 20 percent and watch recovery; oscillation means less Kp and more Ti. Function-test the float-switch interlocks quarterly.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety per IEC 60204-1 / GB/T 5226.1; water supply practice per GB 50015. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.