Wrong Motor Connection Method Causes Star-Delta Start to Burn Out the Motor (High-Power Water Pump)

E41-063 · Motor Selection · High-Power Water Pump · ★★

Problem Symptom

During a star-delta reduced-voltage start of a 75kW pump motor, the circuit breaker tripped at the instant the connection changed from star to delta. Inspection showed the motor winding short-circuited and burned out.

Root Cause

The 75kW motor nameplate specifies a delta connection (rated current 140A, voltage 380V), but during installation the wiring sequence of U1-V1-W1 and U2-V2-W2 among the six leads was connected wrongly. In star starting the three phase windings each form their own star point; when the star point is not correctly connected, changing over to delta leaves one pair of phase sequences reverse connected, forming a short-circuit loop. In a normal star-delta changeover the winding ends are shorted in star and connected in series head-to-tail in delta. When the correspondence between U1 and V2, V1 and W2, W1 and U2 is confused, a huge circulating current (up to 8~10 times rated current) is generated at the moment of changeover, tripping the breaker and severely burning the winding.

Correct Solution

1) Basic star-delta wiring rule: in the motor terminal box U1-U2 is one phase, V1-V2 is one phase, W1-W2 is one phase
2) Star connection: short U2+V2+W2 and connect U1-V1-W1 to the supply
3) Delta connection: connect U1-V2, V1-W2 and W1-U2 respectively
4) After wiring, measure the DC resistance of each phase with a multimeter; the values should be equal (deviation ≤2%)
5) The phase sequence must be verified with a phase sequence meter before starting
6) Electrical protection settings: thermal relay setting = motor rated current ×1.05 (star-delta start)
7) Where possible use a soft starter (programmable current limiting plus ramped start, avoiding the risk of connection errors)

Checklist

References

FT_12_Motor Selection Systematization