E41-592 · Bearing Selection · High Temperature Fan Bearing Housing (200℃) · ★★★★
The bearing housing of a high-temperature fan (flue gas at 200℃) used a water-cooled structure, but during operation the bearing temperature still reached 85℃ (the allowable limit is 90℃) and repeatedly approached the alarm value.
The water-cooled cavity of the housing was designed as an annular water channel (section 20×20mm), with cooling water inlet temperature 32℃ and outlet 45℃. The heat removal is calculated as: cooling water flow Q=5L/min, temperature difference ΔT=13℃, heat removal P=Q×ρ×Cp×ΔT=5/60×1000×4180×13≈4.5kW. The heat absorbed by the housing from the hot side (conduction from the fan shaft plus bearing friction heat) is about 3kW, so in theory the 4.5kW of cooling capacity is sufficient. The actual reason the bearing reached 85℃ is: (1) the water-cooled cavity cools the outer wall of the housing directly, but the contact thermal resistance between the bearing outer ring and the housing bore is large (an air gap thermal resistance of about 0.01m²·K/W), so the heat transfer from bearing to housing is inefficient; (2) the cooling channel is close to the bottom of the housing (cooling the outer wall) while the heat is concentrated in the housing bore (close to the bearing), so the heat conduction path is long and the temperature difference large. The measured outer wall temperature of the housing was 45℃ and the bore temperature 80℃, a difference of 35℃.
1) Water-cooled housing design: the cooling channel must be close to the housing bore (within 10mm of the bore);
2) Increase the cooling water channel section to 30×30mm and raise the flow to 10L/min;
3) Change to a spiral channel structure (the cooling water flows spirally around the housing, giving uniform cooling);
4) Fit a temperature sensor on the housing (directly measuring the bearing outer ring temperature);
5) Use high-temperature bearing steel (Cr4Mo4V, rated to 350℃) or fit an insulating spacer.
FT_Bearing Design Handbook