E41-148 · Sensor Electrical Selection · Textile Winding Tension Control · ★★★★
During operation the winding machine's tension sensor zero drifts; the initial set tension of 500 cN drifts to 650 cN after 2 hours of running, and the unstable winding tension causes fabric wrinkles.
The tension sensor is strain-gauge type (range 0~1000 cN, accuracy 0.5%FS). Its zero temperature-drift coefficient is about 0.02%FS/℃, i.e., 0.2 cN/℃. When the workshop temperature rises from 20℃ in the morning to 35℃ at noon (15℃ difference), the zero drift is Δzero = 0.2×15 = 3 cN, only 0.3%FS, seemingly tiny. But the sensor is actually mounted near the machine heat source (motor + heating roller); its body temperature rises from 20℃ to 50℃ (30℃ difference) and the zero drift becomes Δzero = 0.2×30 = 6 cN. Adding strain-gauge creep under prolonged load (about 0.1%FS/h ≈ 1 cN/h), after 2 hours the creep drift is about 2 cN. Adding the amplifier temperature drift (0.05%FS/℃ × 30℃ = 15 cN), the total drift ≈ 6 + 2 + 15 = 23 cN, shifting tension from 500 cN to 523 cN. The actual 650 cN indicates additional mechanical factors (guide-roll thermal expansion changing the force arm).
① Mount the tension sensor away from heat sources (or add a heat shield)
② Control sensor body temperature within ±2℃ (add a water-cooled base)
③ Select a low-drift sensor (temperature drift ≤0.005%FS/℃)
④ Periodic auto-calibration: perform a zero calibration on each roll change
⑤ Add a temperature-compensation algorithm in the PLC program (correct zero based on sensor temperature)