Knowledge Base › Selection Error Cases › Improper Double-Sheet Detector Sensitivity Calibration Causing Frequent False Alarms (Automatic Feeder

Improper Double-Sheet Detector Sensitivity Calibration Causing Frequent False Alarms (Automatic Feeder)

E41-150 · Sensor Electrical Selection · Automatic Feeder Double-Sheet Detection · ★★★

Problem Description

The automatic feeder's double-sheet detector frequently gives false alarms (no alarm when two sheets are present, but alarms on a single sheet), with a false-alarm rate of about 20%, severely hurting feeding efficiency.

Root Cause

Double-sheet detection uses an ultrasonic through-beam sensor that judges double sheets by the attenuation difference of ultrasound passing through two sheets versus one. The sensor sensitivity was calibrated at the factory against 80 g/m² standard paper, but in practice many paper grades are used (60~120 g/m²) with different ultrasonic attenuation. The attenuation of a single 60 g/m² sheet is close to that of a single 120 g/m² sheet, causing misjudgment. Moreover, the sensitivity knob was accidentally bumped (by an operator wiping the unit), drifting sensitivity from the set 70% to 85%. At 85% sensitivity, a thick single sheet (120 g/m²) is misjudged as double (exceeding the 80% threshold), while a thin double sheet (60 g/m² × 2) has attenuation below the threshold (about 75%) and goes undetected.

Corrective Solution

① Recalibrate double-sheet detection for the actual paper basis weight
② Calibration method: place one sheet → press the "set" key to memorize the reference value
③ Then place two sheets → confirm the alarm output
④ Recalibrate when switching to a different paper grade
⑤ Add a sensitivity locking knob (to prevent accidental bumps) + calibration indicator LED
⑥ Or select an auto-calibrating sensor (one-touch auto tuning)