E41-457 · Other Selection · Steam Pipe Flange Leakage · ★★★
A steam pipe (1.0MPa, 180℃) leaked at the flange joint after 3 years of service; on dismantling, the graphite tape of the spiral-wound gasket (304 + graphite) was found to have oxidized and become loose.
The spiral-wound gasket (304 stainless steel tape + flexible graphite tape) runs long-term in 180℃ steam; the graphite tape slowly oxidizes under the combined action of high temperature and oxygen (trace dissolved oxygen in the steam) (oxidation begins at about 450℃), but the oxidation rate at 180℃ is very slow. The actual cause of failure: the gasket compression was uneven during installation (compression ratio ranging from 15% to 35%); where the graphite tape was over-compressed (>30%), the graphite structure was destroyed and its resilience dropped. Under steam pressure fluctuation (±0.2MPa) and temperature cycling (thermal shock during start-stop), the gasket lost its elastic recovery capability, and the flange faces separated slightly under thermal deformation (about 0.05mm), forming a leakage path. Steam jetting out of the leakage path (velocity about 30m/s) eroded the graphite tape and accelerated local failure.
① Installation compression ratio of the spiral-wound gasket: 15~30% (excessive compression destroys the graphite structure)\n② Tighten the flange bolts with a torque wrench in a diagonal pattern in 3 passes (M20, torque 250Nm)\n③ Replace the gasket of a high-temperature pipe periodically (every 3 years or at overhaul)\n④ Select a spiral-wound gasket with an outer ring (the outer ring limits compression, preventing over-compression)\n⑤ Or switch to a grooved combination gasket (stainless steel grooved core + graphite covering, good resistance to thermal shock)
FT_Machine Design Handbook