Knowledge Base › Selection Error Cases › Interference caused by incorrect shielding-layer grounding of control cables (shield grounding)

Interference caused by incorrect shielding-layer grounding of control cables (shield grounding)

E41-798 · Other Selection · Shield Grounding Error · ★★★★

Problem Description

The VFD control cable (shielded type, shield grounded at both ends) caused the PLC analog input signal to fluctuate ±10% (required ±1%) during VFD operation.

Root Cause

The VFD control cable shield was grounded at both ends (PLC end and VFD end). The VFD-side high-frequency common-mode current (frequency 10–100 MHz, amplitude about 100 mA) flowed through the shield → PLC-side ground wire → earth, producing a common-mode voltage drop on the shield U_cm = I×Z_cm = 0.1×10 = 1 V (Z_cm ≈ 10 Ω). This voltage coupled into the signal wire through the distributed capacitance between shield and signal wire (about 100 pF/m × 10 m = 1000 pF), generating an interference signal U_n = U_cm×C_c/(C_c+C_s) = 1×1000/(1000+100) = 0.91 V (C_s ≈ 100 pF is the signal-wire-to-ground capacitance), producing ±9.1% error in the 0–10 V analog signal. Correct practice: ground the shield at one end only (ground at the PLC side, leave the VFD side floating) to break the common-mode current loop.

Corrective Solution

① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning

Checklist