E44-1113 · Miscellaneous · Relief Valve · ★★
Stuck, open, leaking
[Mechanism] The relief valve plug sticks and cannot re-seat, so it stays open and leaks, failing to hold system pressure.
[Calculation] The seat is stuck open by a 0.5mm gap, leakage is 5L/min, and system pressure drops from 1.0 to 0.6MPa.
[Design Omission] No valve cleaning, no set-pressure check, no seal replacement, and no closure test.
1) Clean the valve to prevent sticking (remove foreign matter), since sticking holds it open and cleaning lets it close, restoring closure;
2) Check set pressure (set to 1.0MPa), since a wrong setting opens it and a correct value lets it seat, restoring pressure holding;
3) Replace the seals (new parts for worn ones), since aged seals cause sticking and new ones seal, restoring re-seating;
4) Hold temperature ≤120℃ (to prevent sticking), since high temperature causes seizure and temperature control protects it, suppressing sticking;
5) Run a closure test (leakage ≤0.1L/min), since without proof tightness is unknown and a measured test confirms it, setting closure on data;
6) Fit pressure monitoring (alarm on venting), since an open valve first shows as pressure drop for early warning, monitoring leakage;
7) Set a cleaning interval (quarterly), since long service causes sticking and scheduled cleaning prevents it, keeping it free in service;
8) Write valve cleaning and pressure check into the relief-valve card, since opening stems from a dirty, stuck valve, closing the loop on the card.
GB/T 12241-2005 Safety valves