E44-410 · Two-Phase Flow and Gas Binding · Control Valve High Pressure Drop with Gas · ★★
Gas downstream of the valve worsens cavitation, the trim pits run 0.6mm deep, the flow characteristic distorts, and internal leakage appears.
[Mechanism] Gas lowers the pressure downstream of the valve further, and collapsing vapor bubbles erode the trim.
[Calculation] Erosion distorts the characteristic and drifts Cv.
[Design Omission] The pressure drop was not staged and no anti-cavitation valve was used — the cause of the control-valve cavitation.
1) Limit the single-stage pressure drop to Δp/p1 ≤0.3 to avoid cavitation; gas worsens erosion, pits 0.6 and distortion, so control the drop;
2) Switch to a multi-stage pressure-reducing cage trim; a single seat with a large drop erodes easily, so stage the drop;
3) Weld hard-facing alloy on the trim for erosion resistance; the base metal erodes and drifts, so hard-face it;
4) Vent upstream first to cut the gas content; gas aids erosion, so vent it;
5) Periodically measure Cv drift to detect erosion; erosion causes drift, so monitor it;
6) Add downstream diffusion to stabilize flow; the vena contracta scours, so diffuse;
7) Choose an erosion-resistant valve type; erosion comes with noise, so pick the best type;
8) Write the pressure-drop ratio into the sizing; the original lack of control was the cause of erosion, so gate it at design stage.
GB/T 4213-2008 Pneumatic industrial-process control valves