E44-414 · Two-Phase Flow and Gas Binding · Steam Line Condensate Buildup · ★★
Liquid collecting at low points of the steam line shrinks the gas-flow area by 50%, doubles the pressure drop, and drops the end pressure by 0.12MPa.
[Pooling] Low-point liquid occupies the section, shrinking the gas path and raising resistance.
[Pressure Drop] Doubled pressure drop drops the end pressure 0.12.
[Design Omission] No steam trapping to drain the accumulation and no slope were provided — the cause of the liquid blockage.
1) Slope the piping and fit steam traps at low points for continuous draining; liquid takes 50% of the area, doubles the drop and loses 0.12MPa, so drain to keep the flow area;
2) Slope ≥0.003 toward the drain point; a flat line easily pools, so lay it sloped;
3) Add a gas-liquid separator with periodic draining; liquid travels with gas, so separate it;
4) Fit a trap at the end; liquid gathers at the end, so drain there;
5) Check two-phase pressure drop with liquid; the pure-gas formula under-predicts, so compute accurately;
6) Vent high points and drain low points for double protection; both gas and liquid are hazards, so protect both;
7) Periodically check for pooling; pooling gradually hardens to notice, so inspect for liquid;
8) Write condensate draining into the design; the original lack of drainage was the root cause of the blockage, so gate it at design stage.
GB/T 5657-2013 Technical specifications for centrifugal pumps