E44-020 · Filter Clogging and Contamination · Cooling-Water Y-Strainer · ★★
The strainer was 60% clogged, dropping flow from 50m³/h to 28; with a large heat-exchange temperature difference, the equipment overheated.
[Flow Orifice Reduction] Clogging cuts the effective screen area to A=0.4A0, so velocity v=Q/A rises 2.5× and resistance ∝v² rises 6×.
\n[Flow] Downstream flow was forced down to 28 to hold the pressure drop, leaving insufficient cooling.
\n[Design Omission] No Δp gauge fitted and no scheduled cleaning; the clogged screen caused the flow drop.
1) Fit a Δp gauge on the strainer to monitor clogging; since clogging cuts A to 0.4A0 and raises resistance ∝v² by 6×, an out-of-limit Δp signals blockage;
\n2) Set a cleaning interval and clean on schedule; waiting until 60% clogged is too late — flow had already dropped from 50 to 28 — so scheduled cleaning prevents it;
\n3) Install a parallel standby strainer for online switch-over; cleaning without shutdown keeps the line running;
\n4) Select the mesh rating to match the debris in the medium; too fine clogs easily and too coarse does not filter clean, so the mesh is matched to the dirt load;
\n5) Add a settling tank at the inlet to cut the load; letting large debris settle first reduces the screen burden and extends the cleaning interval;
\n6) Alarm online on flow rate and temperature difference; a flow drop raises the ΔT and overheats equipment, so anomalies trigger an alarm;
\n7) Verify flow reaches design value during commissioning; restored flow confirms the line is clear, so it passes acceptance;
\n8) Write the cleaning interval into the maintenance card; the absence of an interval caused the clogging, so maintenance is based on a schedule.
GB/T 14382-2008 Y-strainers for piping