E44-699 · Hydraulic System Contamination and Crawling · Coolers · ★★
Blocked, high temperature, >60℃
[Mechanism] A blocked cooler lets the oil overheat.
[Calculation] Blockage drives the oil temperature to >60℃.
[Design Omission] No cleaning, no back-flushing, and no inspection - the root cause of blockage.
1) Clean the cooler to remove scale (chemical + high-pressure, scale <0.5mm); blockage originally cut the heat-transfer coefficient K by 40% and pushed the temperature to >60℃, so descaling cools the oil;
2) Provide back-flushing (periodic reverse flow, each shift); deposits cause blockage, and back-flushing keeps the cooler clean, preventing it;
3) Raise the cooling water flow (water flow +20%); low flow leaves the oil hot, and raising the flow dissipates the heat, controlling the temperature;
4) Dose anti-scaling treatment (scale inhibitor 3ppm); scale blocks the cooler, and dosing suppresses it, preventing scale buildup;
5) Monitor the blockage pressure drop (alarm at Δp >0.1MPa); gradual blockage is quantified by the pressure drop, which triggers cleaning, giving early warning;
6) Control the inlet water temperature (≤32℃); warm inlet water leaves the oil hot, and controlling it stabilizes the cooling source;
7) Inspect the cooler on a fixed schedule (each quarter, check for blockage); gradual blockage is invisible, and inspection catches it, giving early warning;
8) Write descaling and back-flushing into the maintenance card (back-flush interval); the original failure to clean was the root cause, so closing the loop in maintenance serves as the gate.
GB/T 3766-2015 General technical conditions for hydraulic systems